Permit Number: TC-COM-0426-00559
Parcel: 11706078C

Review Status: Requires Resubmit

Review Details: COMMERCIAL PDSD SIMPLE REVIEW v.1

Permit Number - TC-COM-0426-00559
Review Name: COMMERCIAL PDSD SIMPLE REVIEW v.1
Review Status: Requires Resubmit
Review Date Reviewer's Name Type of Review Description Status Comments
04/16/2026 Bldg Permits - Post Review Express PENDING ASSIGNMENT
04/16/2026 Commercial Electrical Express REQUIRES RESUBMIT Commercial Electrical Review TC-COM-0426-00559 (211 N 4TH AV Unit:UNIT 323 TUCSON, AZ 85705)
Plan review for the above referenced structure has been completed. This letter reflects comments to be addressed. Provide updated Plans/calculations and a written response Letter to each of the notated items indicating action taken. Resubmitted plans that do not contain a written response Letter addressing each of the notated items indicating action taken, may be delayed until response letter is received.
Code reference, 2024 International Building Code (IBC), 2023 National Electrical Code (NEC).

Contact Jeremy Hamblin with any questions: Jeremy.hamblin@tucsonaz.gov

1. The provided notes indicate that 2 devices in the kitchen will be moved. There is also a note regarding future ork in the kitchen. Please provide a basic electrical floorplan of the kitchen that shows this work. The notes are not clear.
2. Do not submit the full construction plans from the entire building. This will not be reviewed. Provide updated plans showing only the work being done under this permit.
04/16/2026 PDSD Application Completeness Express REVIEW COMPLETED