Permit Review Detail
Review Status: Requires Resubmit
Review Details: COMMERCIAL REVIEW - LIMITED v.1
Permit Number - TC-COM-0426-00502
Review Name: COMMERCIAL REVIEW - LIMITED v.1
Review Status: Requires Resubmit
| Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
|---|---|---|---|---|---|
| 04/29/2026 | Commercial Building | APPROVED | |||
| 04/30/2026 | Site Zoning | APPROVED | |||
| 04/21/2026 | Water - PDSD | APPROVED | |||
| 04/17/2026 | Site Engineering | NOT REQUIRED | |||
| 04/30/2026 | Bldg Permits - Post Review Express | PENDING ASSIGNMENT | |||
| 04/22/2026 | Commercial Electrical | REQUIRES RESUBMIT | Commercial Electrical review TC-COM-0426-00502 (2458 N CAMPBELL AV Unit:UNIT B TUCSON, AZ 85719) Plan review for the above referenced structure has been completed. This letter reflects comments to be addressed. Provide updated Plans/calculations and a written response Letter to each of the notated items indicating action taken. Resubmitted plans that do not contain a written response Letter addressing each of the notated items indicating action taken, may be delayed until response letter is received. Code reference, 2024 International Building Code (IBC), 2023 National Electrical Code (NEC), 2012 Outdoor Lighting Code (OLC). https://www.tucsonaz.gov/files/sharedassets/public/v/1/pdsd/documents/building-code/2012_outdoor_lighting_code_.pdf Contact Jeremy Hamblin with any questions: Jeremy.hamblin@tucsonaz.gov 1. Electrical floor plan that shows the location of all new, modified and existing electrical work. Mark each electrical device, outlet, light, etc. as existing, new, or relocated. 2. Provide electrical load calculations, for the Main Service Panel, Per NEC 220.40. 3. Provide a panel schedules, showing the circuits that are being modified, added or removed or existing. NEC arts;300 and 408.4. Include panel bus rating and A.I.C. rating. IBC 107.1. 4. Designate the circuit number on the electrical plans, that corresponds to the panel schedule, at the location of each, new or modified light fixture, receptacle, and equipment disconnect switch, NEC arts;300 and 408.4. IBC 107.1. 5. Provide complete compliance with the 2018 IECC for the interior lighting, including sensors and lighting controls as required. (typically COMcheck.) Additional comments may be forthcoming with complete electrical plans. |
||
| 04/21/2026 | Commercial Mechanical | REQUIRES RESUBMIT | 1. The ventilation for a barber shop includes a requirement for 0.5 CFM of exhaust per square foot. Verify that the amount of outside air introduced into the building is approximately equal to the amount of air being exhausted from the building. Reference: Section 403.1 and Table 403.3.1.1, IMC 2024. 2. Provide heating and cooling load calculations to justify the heating/cooling capacities of the specified HVAC unit. Reference: Section C403.1.1 and C403.3.1, IECC 2024. 3. Show that the proposed single-phase air conditioning equipment, less than 65,000 BTU/H meets the minimum performance requirements set by the US Department of Energy Code of Federal Regulations DOE 10 CFR 430 (e.g., SEER2). Reference: Section C403.3.2, IECC 2024. If you have any questions about this review comment, I can be reached at Robert.Sherry@tucsonaz.gov. |
||
| 04/21/2026 | Commercial Plumbing | REQUIRES RESUBMIT | Verify that the distance from the hot water source to the hot water termination for the public lavatories complies with the requirements of Section C404.5.1, IECC 2024 (i.e., the maximum distance from the termination of the hot water source to the lavatory is 24” for a ½” supply). If you have any questions about this review comment, I can be reached at Robert.Sherry@tucsonaz.gov. |
||
| 04/29/2026 | Fire New Construction | REVIEW COMPLETED | |||
| 04/15/2026 | PDSD Application Completeness Express | REVIEW COMPLETED |