Permit Review Detail
Review Status: Requires Resubmit
Review Details: COMMERCIAL REVIEW - FULL v.1
Permit Number - TC-COM-0426-00501
Review Name: COMMERCIAL REVIEW - FULL v.1
Review Status: Requires Resubmit
| Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
|---|---|---|---|---|---|
| 05/04/2026 | Commercial Building Standard | APPROVED | |||
| 04/20/2026 | Outdoor Lighting Standard | NOT REQUIRED | No modifications to the outdoor lighting. | ||
| 05/05/2026 | Bldg Permits - Post Review Express | PENDING ASSIGNMENT | |||
| 04/27/2026 | Commercial Electrical Standard | REQUIRES RESUBMIT | Commercial Electrical Review TC-COM-0426-00501 (265 W VALENCIA RD TUCSON, AZ 85706) Plan review for the above referenced structure has been completed. This letter reflects comments to be addressed. Provide updated Plans/calculations and a written response Letter to each of the notated items indicating action taken. Resubmitted plans that do not contain a written response Letter addressing each of the notated items indicating action taken, may be delayed until response letter is received. Code reference, 2024 International Building Code (IBC), 2023 National Electrical Code (NEC), 2012 Outdoor Lighting Code (OLC). https://www.tucsonaz.gov/files/sharedassets/public/v/1/pdsd/documents/building-code/2012_outdoor_lighting_code_.pdf Contact Jeremy Hamblin with any questions: Jeremy.hamblin@tucsonaz.gov 1. Provide conductor sizing calculations per NEC 690.8. Show conductor ampacity derates (temperature) and corrections (current carrying conductors) according to NEC 310.15. City of Tucson amendment to NEC: Section 310.15 Ampacity Tables. REVISE Section by ADDING the following: 310.15 (B)(3) Outdoor Ambient Temperature. The ambient temperature for application of Tables 310.15 (B)(1)(1) and 310.15 (B)(1)(2) for outdoor installations shall be not less than 45º C (113º F). |
||
| 04/27/2026 | Site Engineering Standard | REQUIRES RESUBMIT | Permit: TC-COM-0426-00501 – Commercial Solar Permit Location: 265 W VALENCIA RD Review Date: 4/27/2026 This plan has been reviewed for compliance with applicable development criteria in the City of Tucson Unified Development Code (UDC) Administrative Manual (AM) Section 2-06 and Technical Manual (TM) Section for waste management, Pedestrian Access, Hydrology -Retention/Detention Requirements, and all site standard code. Drainage Manual Link: https://www.tucsonaz.gov/files/sharedassets/public/v/1/pdsd/documents/engineering-code/cot-drainage… Design standards for Stormwater Detention and Retention Link: https://www.tucsonaz.gov/files/sharedassets/public/v/1/pdsd/documents/engineering-code/updated-rete… Overall, for application submittal requirements, see Administrative Manual Section 2-06 Site Engineering: 1. This property located at 265 W VALENCIA RD is located entirely within a COT floodplain associated with the Airport Wash and will require a separate floodplain use permit with cost estimate. a. The FPU permit is a separate permit that can be submitted for within the sub-records of this permit. b. For the submission of the FPU permit, please provide a cost estimate form that will break down the total cost into separate lines, separating labor, materials/equipment, and warranties/fees associated with the project. Ensure to have company/contractor letterhead on the document for proper documentation. 2. Site Engineering will be unable to approve permit TC-COM-0426-00501 until the associated FPU permit is approved. It is recommended that the FPU permit process be started and achieve approval and issuance prior to the resubmission of this permit to ensure no project delays and review overlap. If you have any questions or concerns, please contact Joe Macaulay at: Joe.Macaulay@tucsonaz.gov |
||
| 05/05/2026 | Site Zoning Standard | REQUIRES RESUBMIT | PDSD TRANSMITTAL FROM: Krista Hansen Planning & Development Services Department – Zoning Review Section PROJECT: TC-COM-0426-00501 265 W VALENCIA RD (C-1) Roof Top Solar (1st Review) TRANSMITTAL DATE: 5/5/2026 This site is zoned C-1 (UDC Section 4.7.20). Comments: Please resubmit revised drawings along with a detailed response letter which states how all Zoning Review Section comments were addressed. 01. COMMENT: Based on aerial photos, it appears that work has been done on the southeast quadrant of the parcel, including but not limited to pedestrian circulation, landscaping, shade structures, and playground equipment. Zoning was not able to find approved permit documents for these additions. Before this solar permit can be approved, the applicant must apply for a separate permit (Commercial Addition/Alteration Permit) for the shade structures. To address the additional site work, please include a site plan and parking calculations with the building plan set. For questions regarding Zoning comments, please contact me at: Krista.Hansen@tucsonaz.gov |
||
| 05/04/2026 | Fire New Construction Standard | REVIEW COMPLETED | |||
| 04/13/2026 | PDSD Application Completeness Express | REVIEW COMPLETED |