Permit Number: TC-COM-0426-00491
Parcel: 126134680

Address:
4515 E 22ND ST

Review Status: Requires Resubmit

Review Details: COMMERCIAL REVIEW - FULL v.1

Permit Number - TC-COM-0426-00491
Review Name: COMMERCIAL REVIEW - FULL v.1
Review Status: Requires Resubmit
Review Date Reviewer's Name Type of Review Description Status Comments
04/21/2026 Commercial Electrical Standard APPROVED
04/20/2026 Outdoor Lighting Standard APPROVED
04/21/2026 Site Zoning Standard APPROVED
04/21/2026 Water - PDSD Standard APPROVED
04/14/2026 Site Engineering Standard NOT REQUIRED
04/22/2026 Bldg Permits - Post Review Express PENDING ASSIGNMENT
04/20/2026 Commercial Building Standard REQUIRES RESUBMIT ACTIVITY NO. TC-COM-0426-00491
ADDRESS/PARCEL: (4515 E 22ND ST TUCSON, AZ 85711)
Submit your revised drawings along with a detailed response letter, which states how all Building Review Section comments were addressed. Please paste the review comment individually and enter your response directly below it. Please do this for every comment. Review will not proceed without the response letter. The submitted documents were incomplete and a thorough plan review could not be performed. Please be aware, new comments may arise with the next review. Should the above not followed, it may delay your approval. Additionally, please submit complete copies of all permit documents (i.e. plans, calculations, reports, etc.) even if they have not been changed.

Should you have any questions about these Commercial Building comments, I can be reached at Justin.Eder@tucsonaz.gov or 520-837-4976.

COMMENTS:
1. CODE ANALYSIS
a. Please provide a complete code analysis per IBC 107 which will include:
i. Adopted Building Codes
1. Include Local Amendments
2. Please correct the year for the IEBC, the correct year is 2024
3. Please correct the year for the IECC, the correct year is 2024
4. Please add ICC A117.1 - 2017 Accessible and Usable Building and Facilities
ii. Occupancy Classification IBC Chapter 3
1. Should this facility be an S2 with Offices?
iii. Fire Sprinklers Yes / No ________________ If Yes: New____ Existing____ Type NFPA__________ IBC 903, 903.3
iv. Fire Alarm Yes / No _________________ If Yes: New____ Existing____ IBC 907
v. Area Allowable _______________ Actual _______________ IBC 503, 505 through 507 & Table 506.2 1. (Include allowable area calculations per IBC 506) (Include mixed occupancy calculations if applicable)
vi. Occupant Load per Floor Calculation (Identify the use of Fixed or Movable Seats) IBC 1004 & Table 1004.5
1. Please amend plans to show the current design occupant load analysis to specify the individual building area of each room or space that is shown on the plan.
2. Further, enter the name of the space, area square footage, clarify the design occupant load (gross or net s.f. per person used) and the number of occupants for each room or space on the plan, in accordance with the requirements of IBC Table 1004. IBC 107.2.7
vii. Provide the Exit width calculation. Number of Exits Required ____________ (If (2) or more exits required; Egress Plan Required) Provided ____________ IBC 1006, 1007, & Tables 1006.2.1, 1006.3.3, 1006.3.4(1), 1006.3.4(2)
viii. Provide an Egress Plan. Show these information on the Egress Plan including cabinets, furnitures, tables and chairs, displays, equipments, etc. which will reveal the actual exit route.
ix. Enter the distance of travel within the facility and their direction of travel.
x. At the point of exit, enter the required width, the provided width, the distance traveled and the number of occupants exiting.
xi. Required Plumbing Fixtures (Provide calculations for the number of water closets, urinals, lavatories, drinking fountains, and service sinks) IBC 2902 & Table 2902.1
2. ACTUAL AREA/SPACE TENANT OCCUPIES
a. Market on the Move occupies 2.5 bays.
b. The submitted drawings reflect only 1 bay.
c. Include the adjacent bay into the drawings.
i. Include the water damaged ceiling, its removal and replacement.
ii. Include the flooring removal and its replacement.
d. Include the half bay that contains offices.
i. Include all new work being done and work that was done without a permit.
3. DEMISING WALL
a. The demising walls are CMU block with certain fire rating separating the bays with a parapet above the roof providing element to stop fire from jumping from one bay to the next. IBC 402.4.2.1 and IBC 708
b. Where door opening are present connecting these bays, provide door with fire rating that is in compliant with the demising wall’s fire rating.
c. Sheet A-2.0 contains wall details. However, a drawing of the CMU demising wall is not represented. Please provide a drawing of the demising wall reflecting code compliant configuration.
4. TRUSS
a. Please submit the truss diagram, calculation and layout.
5. Please resubmit.
04/21/2026 Commercial Mechanical Standard REQUIRES RESUBMIT 1. Show the size, routing, and termination of the condensate drains for the mini-split indoor units. Reference: Section 307.2.1, IMC 2024 as amended by the City of Tucson.
2. Provide calculations to verify that adequate ventilation will be provided for the office spaces. Reference: Section 403.3.1.1, IMC 2024.
If you have any questions about this review comment, I can be reached at Robert.Sherry@tucsonaz.gov.
04/21/2026 Commercial Plumbing Standard REQUIRES RESUBMIT Revise the hot water service to the lavatory in the eastern restroom so that the distance from the hot water source to the hot water termination for the public lavatory complies with the requirements of Section C404.5.1, IECC 2024 (i.e. termination within 24” for a ½” supply).
If you have any questions about this review comment, I can be reached at Robert.Sherry@tucsonaz.gov.
04/22/2026 Fire New Construction Standard REVIEW COMPLETED
04/10/2026 PDSD Application Completeness Express REVIEW COMPLETED