Permit Number: TC-COM-0426-00491
Parcel: 126134680

Address:
4515 E 22ND ST

Review Status: Requires Resubmit

Review Details: COMMERCIAL REVIEW - FULL REVISION v.1

Permit Number - TC-COM-0426-00491
Review Name: COMMERCIAL REVIEW - FULL REVISION v.1
Review Status: Requires Resubmit
Review Date Reviewer's Name Type of Review Description Status Comments
08/13/2026 Commercial Mechanical Standard APPROVED
08/10/2026 Outdoor Lighting Standard NOT REQUIRED No modifications from the approved plans.
07/29/2026 Site Engineering Standard NOT REQUIRED
08/04/2026 Site Zoning Standard NOT REQUIRED
08/13/2026 Bldg Permits - Post Review Express PENDING ASSIGNMENT
08/11/2026 Commercial Building Standard REQUIRES RESUBMIT Please submit your revised documents and provide a letter with a written response letter addressing each of the comments indicating how the Review comments were resolved. Please note the submittal was incomplete and the plan review was conducted using the information presented. The subsequent review could generate more comments after original comments have been addressed.
Please contact me if you have any questions about the below comments. I can be reached at email mark.masek@tucsonaz.gov

1. Please provide the complete structural calculations used in the design of this project. Calculations shall be prepared, signed, and sealed by the registered design professional responsible for the structural design and shall demonstrate compliance with the applicable provisions of the 2024 International Building Code. The calculations shall support all structural elements, connections, and load paths associated with the proposed work, including any new or modified structural components.
Code References:

2024 IBC Section 107.2.1 – Construction documents shall contain sufficient information to demonstrate compliance with the applicable code.
2024 IBC Section 1603 – Construction documents shall include the required structural design information.
2024 IBC Chapter 16 – Structural design requirements.



Please contact me if you have any questions about the above comments.
Mark Masek
Plans Examiner – Building Safety
Planning and Development Services | City of Tucson
main 520.837.4994
email mark.masek@tucsonaz.gov
08/10/2026 Commercial Electrical Standard REQUIRES RESUBMIT Commercial Electrical Review TC-COM-0426-00491 (4515 E 22ND ST TUCSON, AZ 85711)
Plan review for the above referenced structure has been completed. This letter reflects comments to be addressed. Provide updated Plans/calculations and a written response Letter to each of the notated items indicating action taken. Resubmitted plans that do not contain a written response Letter addressing each of the notated items indicating action taken, may be delayed until response letter is received.
Code reference, 2024 International Building Code (IBC), 2023 National Electrical Code (NEC), 2012 Outdoor Lighting Code (OLC).
https://www.tucsonaz.gov/files/sharedassets/public/v/1/pdsd/documents/building-code/2012_outdoor_lighting_code_.pdf

Contact Jeremy Hamblin with any questions: Jeremy.hamblin@tucsonaz.gov

1. Show a GFCI [NEC 210.8(E)] receptacle outlet on the same level within 25’ of all new exterior HVAC equipment, [NEC 210.63].
08/13/2026 Commercial Plumbing Standard REVIEW COMPLETED
08/11/2026 Fire New Construction Standard REVIEW COMPLETED
07/24/2026 PDSD Application Completeness Express REVIEW COMPLETED
08/13/2026 Water - PDSD Standard REVIEW COMPLETED