Permit Number: TC-COM-0426-00482
Parcel: 112054080

Review Status: Requires Resubmit

Review Details: COMMERCIAL REVIEW - LIMITED v.1

Permit Number - TC-COM-0426-00482
Review Name: COMMERCIAL REVIEW - LIMITED v.1
Review Status: Requires Resubmit
Review Date Reviewer's Name Type of Review Description Status Comments
04/16/2026 Commercial Mechanical APPROVED
04/20/2026 Site Zoning APPROVED
04/16/2026 Water - PDSD APPROVED
04/14/2026 Site Engineering NOT REQUIRED
05/04/2026 Bldg Permits - Post Review Express PENDING ASSIGNMENT
04/21/2026 Commercial Building REQUIRES RESUBMIT Please submit your revised documents and provide a letter with a written response letter addressing each of the comments indicating how the Review comments were resolved. Please note the submittal was incomplete and the plan review was conducted using the information presented. The subsequent review could generate more comments after original comments have been addressed.
Please contact me if you have any questions about the below comments. I can be reached at email mark.masek@tucsonaz.gov
1. Please indicate the specific use of this B occupancy as Outpatient Clinic or an Ambulatory Care Facility under the Project Data, Occupancy IBC 304.1
2. Please amend the plans to provide a metal stud table or structural calculation to demonstrate the metal studs used for interior walls and partitions that exceed 6 feet in height, including their finish materials, shall have adequate strength and stiffness to resist the loads to which they are subjected but not less than a horizontal load of 5 psf. IBC 1607.15
Please contact me if you have any questions about the above comments.
Mark Masek
Plans Examiner – Building Safety
Planning and Development Services | City of Tucson
main 520.837.4994
email mark.masek@tucsonaz.gov
04/15/2026 Commercial Electrical REQUIRES RESUBMIT Commercial Electrical Review TC-COM-0426-00482 (2908 N CAMPBELL AV TUCSON, AZ 85719)
Plan review for the above referenced structure has been completed. This letter reflects comments to be addressed. Provide updated Plans/calculations and a written response Letter to each of the notated items indicating action taken. Resubmitted plans that do not contain a written response Letter addressing each of the notated items indicating action taken, may be delayed until response letter is received.
Code reference, 2024 International Building Code (IBC), 2023 National Electrical Code (NEC).

Contact Jeremy Hamblin with any questions: Jeremy.hamblin@tucsonaz.gov

1. Reference sheet E0.1, General Electrical Notes #43.
a. The provided equipment and room designations indicate that patient care will be provided in the ‘examination rooms’. These spaces are required to meet the requirement of NEC 517. See NEC 517.1, “This article applies to electrical construction and installation criteria in health care facilities that provide services to human beings.”
b. The wiring and electrical equipment in the examining rooms and other patient care areas within the office suite are subject to the requirements of Article 517.
2. Provide a clear list of services provided in these ‘examination rooms’ and the ‘triage’ room. Include any state licensing information associated with this installation.
3. Reference sheet E3.1, Provide accurate measurements from the sink in the ‘Work Area’, to the electrical receptacles on the counter space across from the sink. It appears that some receptacles are within 6 feet of the sink an require GFCI protection, NEC 210.8(B).
4. Reference sheet E3.1, ‘Work Area’. There are 4 receptacles on the counter space that are shown on circuit A-44. The panel schedule shows circuit A-44 as ‘Spare’. Please correct.
04/16/2026 Commercial Plumbing REQUIRES RESUBMIT 1. For the use of PEX tubing, provide a branch tube sizing chart showing the correct size of PEX tubing to be used as a substitute for the copper pipe shown on the drawings. Reference: Sections 303.2 and 604.3, IPC 2024.
2. Verify that the distance from the hot water source to the hot water termination for the public lavatories complies with the requirements of Section C404.5.1, IECC 2018 (e.g. 24” for ½” pipe, see room 115).

If you have any questions about this review comment, I can be reached at Robert.Sherry@tucsonaz.gov.
04/23/2026 Fire New Construction REVIEW COMPLETED
04/09/2026 PDSD Application Completeness Express REVIEW COMPLETED