Permit Number - TC-COM-0426-00479
Review Name: COMMERCIAL REVIEW - FULL v.1
Review Status: In Review
| Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
|---|---|---|---|---|---|
| 04/24/2026 | Commercial Electrical Standard | APPROVED | |||
| 04/09/2026 | Site Engineering Standard | NOT REQUIRED | |||
| 04/24/2026 | Site Zoning Standard | NOT REQUIRED | |||
| N/A | Bldg Permits - Post Review Express | PENDING ASSIGNMENT | |||
| N/A | Commercial Building Standard | PENDING ASSIGNMENT | |||
| N/A | Fire New Construction Standard | PENDING ASSIGNMENT | |||
| 04/28/2026 | Commercial Mechanical Standard | REQUIRES RESUBMIT | ACTIVITY NO. TC-COM-0426-00479 ADDRESS/PARCEL: 7000 S ALVERNON WY TUCSON, AZ 85756 Submit your revised drawings along with a detailed response letter, which states how all comments were addressed. Review will not proceed without the response letter. The submitted documents were incomplete and a thorough plan review could not be performed. Please be aware, new comments may arise with the next review. If you have any questions about these review comments, I can be reached at Sean.Severson@tucsonaz.gov COMMENTS: 1. Please revise the cover sheet to identify the correct applicable codes. The project shall reference the 2024 I-Codes (IBC, IMC, IPC, etc.) as adopted and amended by the City of Tucson. The 2018 IECC reference is correct. 2. Provide heating and cooling load calculations to justify the addition and capacities of the four proposed rooftop units. Reference: Section C403.1.1 and C502.2.3, IECC 2018. |
||