Permit Number: TC-COM-0425-00808
Parcel: 141185950

Review Status: Requires Resubmit

Review Details: COMMERCIAL REVIEW - LIMITED v.1

Permit Number - TC-COM-0425-00808
Review Name: COMMERCIAL REVIEW - LIMITED v.1
Review Status: Requires Resubmit
Review Date Reviewer's Name Type of Review Description Status Comments
05/08/2025 Commercial Building APPROVED
05/07/2025 Site Zoning APPROVED
05/08/2025 Water - PDSD APPROVED
04/24/2025 Outdoor Lighting NOT REQUIRED No changes to outdoor lighting.
05/08/2025 Bldg Permits - Post Review Express PENDING ASSIGNMENT
04/24/2025 Commercial Electrical REQUIRES RESUBMIT Commercial Electrical Review TC-RES-0325-01192 (9110 E 27TH ST TUCSON, AZ 85710)
Plan review for the above referenced structure has been completed. This letter reflects comments to be addressed. Provide updated Plans/calculations and a written response Letter to each of the notated items indicating action taken. Resubmitted plans that do not contain a written response Letter addressing each of the notated items indicating action taken, may be delayed until response letter is received.
Code reference, 2018 International Building Code (IBC), 2017 National Electrical Code (NEC).

1. A signature and date are required as part of the Registrant Seal (Electrical). Section R4-30-304 of the Rules of the Arizona State Board of Technical Registration, states that in addition to signing the seal, the registrant shall include the date the document was sealed.

2. Please resubmit with EOR Seal corrected to include the date signed.
05/08/2025 Commercial Mechanical REQUIRES RESUBMIT Provide calculations to verify that adequate ventilation will be provided for the occupied spaces. Reference: Section 403.3.1.1, IMC 2018.
05/08/2025 Commercial Plumbing REQUIRES RESUBMIT 1. Provide a metering faucet for the lavatory, dispensing a maximum of 0.25 gallons per metering cycle. Verify that the faucet cycle will last for at least 10-seconds. Reference: Section 419.6, IPC 2018, as amended by the City of Tucson and Section 606.4, ICC/ANSI A117.1-09.
2. Provide tempered water for the restroom lavatory using an approved device conforming to ASSE 1070. Reference: Sections 419.5 and 607.1.2, IPC 2018.
3. Verify that the distance from the hot water source to the hot water termination for the public lavatory complies with the requirements of Section C404.5, IECC 2018.
4. Show that the specified design of the water closet seat meets the requirements of Section 425.3, IPC 2018.
5. Provide specifications for the “water dispenser” noted on sheet P1.0. Show the installation of an accessible cup dispenser. The cup dispenser shall be located adjacent to the water dispenser with the dispensing end between 34” and 48” above the finished floor.
05/01/2025 Fire New Construction REVIEW COMPLETED Fire Sprinklers alteration requires a separate submittal-permit.
04/23/2025 PDSD Application Completeness Express REVIEW COMPLETED