Permit Review Detail
Review Status: Requires Resubmit
Review Details: COMMERCIAL REVIEW - LIMITED v.4
Permit Number - TC-COM-0425-00808
Review Name: COMMERCIAL REVIEW - LIMITED v.4
Review Status: Requires Resubmit
| Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
|---|---|---|---|---|---|
| 05/20/2025 | Commercial Electrical | APPROVED | |||
| 06/02/2025 | Commercial Mechanical | APPROVED | |||
| 06/02/2025 | Bldg Permits - Post Review Express | PENDING ASSIGNMENT | |||
| 06/02/2025 | Commercial Plumbing | REQUIRES RESUBMIT | 1. An ASSE thermostatic mixing valve is designed to control the temperature of a water distribution system at the hot water source. An ASSE 1070 thermostatic mixing valve is designed to control the temperature of the water at a fixture. An ASSE 1017 thermostatic mixing valve may not be used where an ASSE 1070 thermostatic mixing valve is required. [Initial comment: Provide tempered water for the restroom lavatory using an approved device conforming to ASSE 1070. Reference: Sections 419.5 and 607.1.2, IPC 2018.] 2. Comment not resolved; show the installation of an accessible cup dispenser. [Initial comment: Provide specifications for the “water dispenser” noted on sheet P1.0. Show the installation of an accessible cup dispenser. The cup dispenser shall be located adjacent to the water dispenser with the dispensing end between 34” and 48” above the finished floor.] |
||
| 05/19/2025 | PDSD Application Completeness Express | REVIEW COMPLETED |