Permit Number: TC-COM-0425-00808
Parcel: 141185950

Review Status: Requires Resubmit

Review Details: COMMERCIAL REVIEW - FULL REVISION v.1

Permit Number - TC-COM-0425-00808
Review Name: COMMERCIAL REVIEW - FULL REVISION v.1
Review Status: Requires Resubmit
Review Date Reviewer's Name Type of Review Description Status Comments
06/25/2025 Bldg Permits - Post Review Express PENDING ASSIGNMENT
06/25/2025 Commercial Electrical Standard REQUIRES RESUBMIT Commercial Electrical Review TC-COM-0425-00808 (10165 E OLD VAIL RD Unit:UNIT 141 TUCSON, AZ 85747)
REV1: Add temporary construction power.
Plan review for the above referenced structure has been completed. This letter reflects comments to be addressed. Provide updated Plans/calculations and a written response Letter to each of the notated items indicating action taken. Resubmitted plans that do not contain a written response Letter addressing each of the notated items indicating action taken, may be delayed until response letter is received.
Code reference, 2018 International Building Code (IBC), 2017 National Electrical Code (NEC).

1. Provide At least one 125-volt, single-phase, 15- or 20-ampere-rated receptacle outlet shall be installed in an accessible location within 7.5 m (25 ft) of the indoor electrical service equipment. The required receptacle outlet shall be located within the same room or area as the service equipment. NEC 210.64.

Contact Jeremy Hamblin with any questions: Jeremy.hamblin@tucsonaz.gov
06/16/2025 PDSD Application Completeness Express REVIEW COMPLETED