Permit Number: TC-COM-0425-00658
Parcel: 12709008C

Review Status: Requires Resubmit

Review Details: COMMERCIAL REVIEW - FULL v.1

Permit Number - TC-COM-0425-00658
Review Name: COMMERCIAL REVIEW - FULL v.1
Review Status: Requires Resubmit
Review Date Reviewer's Name Type of Review Description Status Comments
04/30/2025 Commercial Building Standard APPROVED
04/21/2025 Commercial Electrical Standard APPROVED
05/01/2025 Commercial Plumbing Standard APPROVED
04/17/2025 Site Zoning Standard APPROVED
05/01/2025 Water - PDSD Standard APPROVED
04/21/2025 Outdoor Lighting Standard NOT REQUIRED No changes to outdoor lighting
05/01/2025 Site Engineering Standard NOT REQUIRED
05/01/2025 Bldg Permits - Post Review Express PENDING ASSIGNMENT
05/01/2025 Commercial Mechanical Standard REQUIRES RESUBMIT Please submit your revised documents and provide a letter with a written response letter addressing each of the comments indicating how the Review comments were resolved. Please note the submittal was incomplete and the plan review was conducted using the information presented. The subsequent review could generate more comments after original comments have been addressed.
1. Please amend plans to provide mechanical design and calculations for the new Batting Cage use of this space; to provide the ventilation requirements of Table 403.3.1. 2018 IMC Section 403

Please contact me if you have any questions about these comments.
Mark Masek
Plans Examiner – Building Safety
Planning and Development Services | City of Tucson
main 520.837.4994
email mark.masek@tucsonaz.gov
04/23/2025 Fire New Construction Standard REVIEW COMPLETED Fire extinguishers shall comply with Section 906 of the 2024 International Fire Code.
04/10/2025 PDSD Application Completeness Express REVIEW COMPLETED