Permit Number: TC-COM-0424-00755
Parcel: 14041124E

Review Status: Requires Resubmit

Review Details: COMMERCIAL REVIEW - LIMITED v.2

Permit Number - TC-COM-0424-00755
Review Name: COMMERCIAL REVIEW - LIMITED v.2
Review Status: Requires Resubmit
Review Date Reviewer's Name Type of Review Description Status Comments
05/20/2024 Bldg Permits - Post Review PENDING ASSIGNMENT
05/20/2024 External Reviewers - SAFEBuilt REQUIRES RESUBMIT Structural(S) Reviewer
Kimiyoshi Shimabukuro
kshimabukuro@safebuilt.com
Denied
Reason:
Date Completed : 5/19/2024 5:49:20 AM
1. Provide base column detail. How are the columns anchored based?
2. Any required special inspection per 2018 IBC chapter 17?
3. Show these racks in relation to overall building sections.



Building(B) Reviewer
Kimiyoshi Shimabukuro
kshimabukuro@safebuilt.com
Denied
Reason:
Date Completed : 5/19/2024 5:52:01 AM
1. Clearly state the scope of work for this TC-COM-0424-00755 permit. Any mechanical, plumbing, electrical work in this suite 190? Provide existing and new plans to clarify the scope under this permit.
2. List the applicable City of Tucson codes: Select and provide applicable accessible code.
City of Tucson IBC Local Amendments
• Amendments to the 2018 International Building Code
• Amendments to the 2018 International Existing Building Code
• Amendments to the 2018 International Energy Conservation Code
• Amendments to the 2018 International Fuel Gas Code
• Amendments to the 2018 International Mechanical Code
• Amendments to the 2018 International Plumbing Code
• Amendments to the 2018 International Residential Code
• Amendments to the 2018 International Swimming Pool & Spa Code
• Amendments to the 2017 National Electrical Code
• Amendments to the 2018 International Fire Code
• City of Tucson/Pima County Outdoor Lighting Code
• Arizona Administrative Code Title 18 Chapter 5 for public and semi-public swimming pools
• ICC A117.1 - 2009 Accessible and Usable Buildings and Facilities (by reference)
Adopting Local Amendments to the Building Code is authorized by Ordinance #11590.
3. Any sprinkler and/or alarm system modifications?
4. Provide referenced drawings TC-COM-1023-02375 as reference to this storage rack submittal that it’s referenced in the letter.
5. Provide new life safety and egress plan that locates these shelves in suite 190 applying 2018 International Building Code (Relative International Fire Code – Section 3208 rack storage or is this automated rack storage section 3209?). Provide building code analysis such as required and provided: occupancy group, construction type, sprinkler or alarm system, affected area (SF), occupancy load, exit locations, egress features such as exits, access doorways, common path of egress travel, dead end corridor, remoteness between exists/exit access doors, means of egress illumination, maximum travel distance to exit, exit access width, and ratings of fire separations.
6. Any storage of hazardous materials according to 2018 International Building Code section 414?
7. Do materials listed in 2018 International Building Code table 414.2.5(1) and (2) exceed the maximum allowable quantity per control area?
8. Any storage of solid and liquid hazardous materials per 2018 IBC section 414.5.3?
9. Provide construction documents accordance with 2018 International Fire Code Section 3201.3. The list contains 14 items for construction documents.
10. Storage layout to provide has 9 listed items including commodity location, classification, and clearance between top of storage and the sprinkler deflector for each arrangement. Examples of commodity classification is in 2018 IFC table 3203.8.
11. 2018 IFC section 3205.3 approved “No Smoking” signs shall be conspicuously posted in accordance with Section 310.
12. Show the high pile storage in overall building section. Relative height of the building/roof and clearances of storage.
13. 2018 IFC section 3206.1 fire protection and life safety features for high-piled storage areas shall be in accordance with sections 3206.2 through 3206.11.
14. Show the size of high-piled storage area per 2018 IFC section 3206.3.1 (table 3206.2 select general fire protection and life safety requirements).
15. Show fire apparatus access roads that’s within 150 feet of all portions of the exterior walls of the buildings used for highpiled storage per 2018 IFC section 3206.6 when applicable.
16. Show storage aisle width in accordance with 2018 IBC section 3206.10.1.
17. Show locations of portable fire extinguishers accordance with 2018 IBC section 3206.11.



Mechanical(M) Reviewer
Kimiyoshi Shimabukuro
kshimabukuro@safebuilt.com
Denied
Reason:
Date Completed : 5/19/2024 5:49:58 AM
1. Clearly state the scope of work for this TC-COM-0424-00755 permit. Any mechanical, plumbing, electrical work in this suite 190? Provide existing and new plans to clarify the scope under this permit.



Electrical(E) Reviewer
Kimiyoshi Shimabukuro
kshimabukuro@safebuilt.com
Denied
Reason:
Date Completed : 5/19/2024 5:50:12 AM
1. Clearly state the scope of work for this TC-COM-0424-00755 permit. Any mechanical, plumbing, electrical work in this suite 190? Provide existing and new plans to clarify the scope.
2. Are there emergency or standby power per 2018 IBC section 414.5.2?



Plumbing(P) Reviewer
Kimiyoshi Shimabukuro
kshimabukuro@safebuilt.com
Denied
Reason:
Date Completed : 5/19/2024 5:49:38 AM
1. Clearly state the scope of work for this TC-COM-0424-00755 permit. Any mechanical, plumbing, electrical work in this suite 190? Provide existing and new plans to clarify the scope under this permit.
05/14/2024 Fire New Construction REVIEW COMPLETED
05/10/2024 PDSD Application Completeness REVIEW COMPLETED