Review Date Reviewer's Name Type of Review Description Status Comments
06/17/2024 Bldg Permits - Post Review PENDING ASSIGNMENT
06/17/2024 External Reviewers - SAFEBuilt REQUIRES RESUBMIT Structural(S) Reviewer
Kimiyoshi Shimabukuro
kshimabukuro@safebuilt.com
Denied
Reason:
Date Completed : 6/17/2024 10:13:38 AM
1. Provide base column detail. How are the columns anchored based? (Resolved)

2. 2018 IBC table 1705.3 requires period inspection for anchor places in concrete.

3. Show these racks in relation to overall building sections. Reference drawings XDS-091356-S1C sheet 2 does not show building sections. Sheet 3 specifies 348 1/8” high storage but doesn’t show vertical clearance of building elements within such as ceiling structure and roof.





Building(B) Reviewer
Kimiyoshi Shimabukuro
kshimabukuro@safebuilt.com
Denied
Reason:
Date Completed : 6/17/2024 10:15:29 AM
1. Clearly state the scope of work for this TC-COM-0424-00755 permit. Any mechanical, plumbing, electrical work in this
suite 190? Provide existing and new plans to clarify the scope under this permit. (Resolved)

2. Complete applicable City of Tucson codes: Select and provide applicable accessible code for high piled storage. Installation of 42 bays for free standing rack in S-1 occupancy should comply with applicable building codes with City
of Tucson amendments. Sheet 1 design conditions is partial codes for high piled storage. City of Tucson IBC Local Amendments
• Amendments to the 2018 International Building Code
• Amendments to the 2017 National Electrical Code
• Amendments to the 2018 International Fire Code – Design condition does not reflect this code for high piles storage.

3. Any sprinkler and/or alarm system modifications? (Resolved)

4. Provide referenced drawings TC-COM-1023-02375 as reference to this storage rack submittal that it’s referenced in the letter. (Resolved)

5. Provide new life safety and egress plan that locates these shelves in suite 190 applying 2018 International Building Code Referenced sheet G0.1 shows exit distance of 111’-1” to exit ‘J’ but this is not measured from the most remote point of the high pile racking room. Life safety plan does not show marking on fire department access door: “FIRE DEPARTMENT ACCESS DOOR DO NOT BLOCK.” (2018 IBC section 3206.7.4) The lettering shall be in a contrasting color to the background. Letters shall have a minimum height of 2 inches with a minimum stroke of 3/8” inch.

6. Any storage of hazardous materials according to 2018 International Building Code section 414? (Resolved)

7. Do materials listed in 2018 International Building Code table 414.2.5(1) and (2) exceed the maximum allowable quantity per control area? (Resolved)

8. Any storage of solid and liquid hazardous materials per 2018 IBC section 414.5.3? (Resolved)

9. Provide construction documents accordance with 2018 International Fire Code Section 3201.3. The list contains 14 items for construction documents. Referenced sheet G0.1 life safety plan and XDS-091356-S1C missing items so address: 4.
Commodity clearance between top of storage and the sprinkler deflector for each storage arrangement. 6. Maximum pile volume for each storage array. 7. Location and classification of commodities in accordance with Section 3203.

10. Type of fire suppression and fire detection systems. 11. Location of valves controlling the water supply of ceiling and in-rack sprinklers.

12. Type, location and specifications of smoke removal and curtain board systems.

13. Dimensions and location of transverse and longitudinal flue spaces.

10. Storage layout to provide has 9 listed items including commodity location, classification, and clearance between top of storage and the sprinkler deflector for each arrangement. Examples of commodity classification is in 2018 IFC table 3203.8. The commodity classification document is not provided by the registered design professional per 2018 International Fire Code section 105.4.1. 11. 2018 IFC section 3205.3 approved “No Smoking” signs shall be conspicuously posted in accordance with Section 310. The signage is still missing from provided sheet G0.1.

12. Show the high pile storage in overall building section. Relative height of the building/roof and clearances of storage.

13. 2018 IFC section 3206.1 fire protection and life safety features for high-piled storage areas shall be in accordance with sections 3206.2 through 3206.11.

14. Show the size of high-piled storage area per 2018 IFC section 3206.3.1 (table 3206.2 select general fire protection and life safety requirements). (Resolved)

15. Show fire apparatus access roads that’s within 150 feet of all portions of the exterior walls of the buildings used for highpiled storage per 2018 IFC section 3206.6 when applicable. Fire apparatus access roads are not shown in referenced life
safety plan sheet G0.1.

16. Show storage aisle width in accordance with 2018 IBC section 3206.10.1. (Resolved)

17. Show locations of portable fire extinguishers accordance with 2018 IBC section 3206.11. Sheet G0.1 shows one fire extinguisher but 2018 IFC section 3206.11 states to provide in accordance with section 906 where table 906.3(1) shows 75 feet maximum distance of travel to extinguisher in class A fire hazards.
06/14/2024 PDSD Application Completeness REVIEW COMPLETED