Permit Number: TC-COM-0424-00746
Parcel: 12509012A

Review Status: Requires Resubmit

Review Details: COMMERCIAL REVIEW - FULL v.1

Permit Number - TC-COM-0424-00746
Review Name: COMMERCIAL REVIEW - FULL v.1
Review Status: Requires Resubmit
Review Date Reviewer's Name Type of Review Description Status Comments
05/23/2024 Site Zoning APPROVED
05/21/2024 Site Engineering NOT REQUIRED
05/23/2024 Bldg Permits - Post Review PENDING ASSIGNMENT
05/14/2024 External Reviewers - Stantec REQUIRES RESUBMIT May 9, 2024
1st Review

Intertech Architectural Interiors, Inc.
Attn: Brittany Thrasher Hammond
6089 East Grant Road
Tucson, Arizona 85716

Re: DECIBEL COFFEE WORKS
TENANT IMPROVEMENT

City of Tucson Permit Number: TC-COM-0424-00746
Stantec Project Number: 185215066
Stantec File Number: TUC-24-042

Plan review for the above referenced project has been completed. This letter reflects comments to be addressed. PLEASE send all response to comments back to the City through the permit portal! Responses sent directly to Stantec will be ignored. Also, please submit complete copies of all permit documents (i.e. plans, calculations, reports, etc.) even if they have not been changed. Please cloud and delta all changes and provide a letter with a written response to each of the comments indicating the action taken.

The scope of this review covers the architectural, structural, plumbing, mechanical, and electrical designs as they relate to the codes adopted by the jurisdiction. All features were checked only to the extent allowed by the submittals provided. All portions of this project are assumed to meet or will meet other departmental requirements, conditions, and concerns before permit approval.

Occupancy
Group Construction
Type Area
(Square feet) Occupant
Load Automatic
Fire Sprinklers Fire
Alarms
B V-B 1,143 25 No No
Separate Permits: Signage.
Deferred Submittals: None.
Special Inspections: None.

ARCHITECTURAL COMMENTS

General

1. Please provide proof that this project has been submitted to the Pima County Health Department for permitting. Make sure to incorporate any of their comments into any future submittals.

2. Please indicate that the signage is to be provided as part of this project and are to be submitted as a separate permit (not a deferred submittal).

3. The plan-set indicates the installation of a new mechanical unit on the roof weighing 675lbs. This unit appears to be in a different area of the roof than the original unit. Please provide a structural analysis that indicates the proposed units can be placed at the locations indicated with/without additional reinforcement. [Ref. IBC 2018 Sec. 1604.4] {This comment is also included in the ‘Structural Comments’ section.}

Sheet G1

1. Please revise the occupancy classification under the ‘General Building Summary’ to a Group B occupancy as it conflicts the occupancy classification on sheet G2. [Ref. IBC 2018 Sec. 303.1.1]

Sheet G2

1. The floor plans indicate a scale of 1/64” = 1’. The floor plans are not to this scale. Please revise.

Sheet G3

1. The floor plans indicate a scale of 1/64” = 1’. The floor plans are not to this scale. Please revise.

2. The egress plan indicates egress through an adjacent tenant space. Required egress must not pass through an adjacent tenant space. Please revise the egress plan to show all egress exit access within this proposed tenant space. The adjacent space also appears to be fully enclosed, abandoned, and unoccupied based on satellite images of the property. Egress into this location does not seem feasible based on these conditions. Please clarify the intent and revise plans accordingly. [Ref. IBC 2018 Sec. 1016.2.1]

STRUCTURAL COMMENTS

General

1. The plan-set indicates the installation of a new mechanical unit on the roof weighing 675lbs. This unit appears to be in a different area of the roof than the original unit. Please provide a structural analysis that indicates the proposed units can be placed at the locations indicated with/without additional reinforcement. [Ref. IBC 2018 Sec. 1604.4]

MECHANICAL COMMENTS

General

1. Please provide an energy conservation compliance report for the new mechanical unit. [Ref IECC 2018 Sec. C403]

PLUMBING COMMENTS

Sheet P1.0

1. Please provide the size of the existing grease interceptor and updated calculations in accordance with Section 1003.3 of the 2018 International Plumbing Code as amended by the City of Tucson to verify existing interceptor is adequate for the proposed fixtures.

ELECTRICAL COMMENTS

There are no comments.


Should you have any questions regarding the plan review comments, please contact the plan reviewer listed for the appropriate discipline.

Plans reviewed by:
Trevor Bies,
Senior Plan Reviewer
602-338-9922
trevor.bies@stantec.com
05/05/2024 Fire New Construction REVIEW COMPLETED
04/26/2024 PDSD Application Completeness REVIEW COMPLETED