Permit Number: TC-COM-0424-00704
Parcel: 12201024K

Address:
3924 E GRANT RD

Review Status: Requires Resubmit

Review Details: COMMERCIAL REVIEW - FULL v.4

Permit Number - TC-COM-0424-00704
Review Name: COMMERCIAL REVIEW - FULL v.4
Review Status: Requires Resubmit
Review Date Reviewer's Name Type of Review Description Status Comments
04/01/2025 Bldg Permits - Post Review Express PENDING ASSIGNMENT
04/01/2025 Commercial Mechanical Standard REQUIRES RESUBMIT All of the air supplied to a restroom must be exhausted. Either increase the exhaust flowrate or reduce the amount of supply air. Revise the sequence of operation for the restroom exhaust fan so that all of the air supplied to the restrooms will be exhausted (i.e. all of the air supplied to each restroom is to be exhausted during the hours of operation even if the lights are off). Reference: Section 403.2.1, IMC 2018.
03/11/2025 PDSD Application Completeness Express REVIEW COMPLETED