Review Details: COMMERCIAL REVIEW - FULL v.2
Permit Number - TC-COM-0424-00704
Review Name: COMMERCIAL REVIEW - FULL v.2
Review Status: Requires Resubmit
Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
---|---|---|---|---|---|
08/28/2024 | Commercial Plumbing | APPROVED | |||
08/23/2024 | Commercial Structural | APPROVED | |||
08/28/2024 | Bldg Permits - Post Review | PENDING ASSIGNMENT | |||
08/26/2024 | Commercial Mechanical | REQUIRES RESUBMIT | 1. Ventilation is required for all occupied areas. Revise the calculations to determine the required ventilation for the suite. See Section 403.3.1.1.2.3, IMC 2018 to learn how to calculate the ventilation for multiple zone recirculation systems. [Initial comment: The occupant load used to calculate the required ventilation is not necessarily the same as the occupant load used for calculating exiting requirements. The occupant load used for calculating the minimum required ventilation is to be based on Table 403.3.1.1, IMC 2018 or an approved engineering analysis of the specific occupancy type. Reference: Section 403.3.1.1, IMC 2018.] 2. The Ez value for a heat pump is 1.0, not 0.5. [Initial comment: The Ez value for a heat pump supplying warm air from the ceiling and with a ceiling return can be 1.0 because the supply air is between 85°F and 92°. See footnote (f), Table 403.3.1.1.1.2, IMC 2018.] 3. Type II hoods are required for electric convection ovens if the HVAC system has not been designed to accommodate the heat and moisture produced by the ovens. If a Type II hood is not required, the kitchen is required to have an exhaust fan to exhaust a minimum of 0.70 CFM per square foot. The area to be exhausted is based on 100 square feet per cooking appliance (e.g. a single cooking appliance would require 70 CFM of exhaust). Reference: Section507.3, IMC 2018. [Initial comment: Provide an exhaust fan for the Type I hood that complies with Section 506.5.1, IMC 2018 and is listed and labeled for the application (i.e. UL 762). The fan discharge shall not impinge onto the roof. Reference: Sections 506.5 and 506.5.3, IMC 2018.] |
||
07/30/2024 | PDSD Application Completeness | REVIEW COMPLETED |