Microfiche records prior to 2006 have not been completely digitized and may not be available yet on PRO. If you can not find what you are looking for please submit a records request.
Permit Review Detail
Review Status: Requires Resubmit
Review Details: COMMERCIAL REVIEW - LIMITED v.5
Permit Number - TC-COM-0424-00670
Review Name: COMMERCIAL REVIEW - LIMITED v.5
Review Status: Requires Resubmit
Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
---|---|---|---|---|---|
07/16/2024 | Commercial Mechanical | APPROVED | |||
07/16/2024 | Bldg Permits - Post Review | PENDING ASSIGNMENT | |||
07/16/2024 | Commercial Plumbing | REQUIRES RESUBMIT | Table 402.4(2), IFGC 2018 is for use with natural gas systems having an initial pressure of less than 2 PSIG and a maximum pressure drop of 0.5” water and is based on systems with only four elbows. Additional developed length would have to be added to account for more complex piping systems. Based on Table 402.4(2), IFGC 2018, a 2” Schedule 40 pipe with a developed length would only allow a maximum flow of 704 CFH with a pressure drop of 0.5” water (the 1860 CFH value comes from Table 402.4(3), IFGC 23018). Recalculate the size of the natural gas distribution system. | ||
06/28/2024 | PDSD Application Completeness | REVIEW COMPLETED |