Permit Review Detail
Review Status: Requires Resubmit
Review Details: COMMERCIAL REVIEW - LIMITED v.1
Permit Number - TC-COM-0424-00670
Review Name: COMMERCIAL REVIEW - LIMITED v.1
Review Status: Requires Resubmit
Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
---|---|---|---|---|---|
05/03/2024 | Commercial Building | APPROVED | |||
05/01/2024 | Commercial Electrical | APPROVED | |||
04/30/2024 | Site Zoning | NOT REQUIRED | |||
05/03/2024 | Bldg Permits - Post Review | PENDING ASSIGNMENT | |||
05/02/2024 | Commercial Mechanical | REQUIRES RESUBMIT | Revise detail 2/M4.0. Condensate drains may not terminate over a roof drain or gutter unless the roof drain or gutter terminates at or below grade in an area capable of absorbing the condensate flow without surface drainage. Reference: Section 307.2.1, IMC 2018, as amended by the City of Tucson. | ||
04/17/2024 | PDSD Application Completeness | REVIEW COMPLETED |