Permit Number: TC-COM-0424-00670
Parcel: 12512080A

Review Status: Requires Resubmit

Review Details: COMMERCIAL REVIEW - LIMITED v.1

Permit Number - TC-COM-0424-00670
Review Name: COMMERCIAL REVIEW - LIMITED v.1
Review Status: Requires Resubmit
Review Date Reviewer's Name Type of Review Description Status Comments
05/03/2024 Commercial Building APPROVED
05/01/2024 Commercial Electrical APPROVED
04/30/2024 Site Zoning NOT REQUIRED
05/03/2024 Bldg Permits - Post Review PENDING ASSIGNMENT
05/02/2024 Commercial Mechanical REQUIRES RESUBMIT Revise detail 2/M4.0. Condensate drains may not terminate over a roof drain or gutter unless the roof drain or gutter terminates at or below grade in an area capable of absorbing the condensate flow without surface drainage. Reference: Section 307.2.1, IMC 2018, as amended by the City of Tucson.
04/17/2024 PDSD Application Completeness REVIEW COMPLETED