Permit Review Detail
Review Status: Requires Resubmit
Review Details: COMMERCIAL REVIEW - FULL v.3
Permit Number - TC-COM-0424-00665
Review Name: COMMERCIAL REVIEW - FULL v.3
Review Status: Requires Resubmit
| Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
|---|---|---|---|---|---|
| 01/30/2025 | Commercial Electrical | APPROVED | |||
| 02/06/2025 | Commercial Mechanical | APPROVED | |||
| 02/10/2025 | Bldg Permits - Post Review Express | PENDING ASSIGNMENT | |||
| 02/06/2025 | Commercial Plumbing | REQUIRES RESUBMIT | Comment not addressed. Cleanout #6 on sheet UT01 and sheet P1.1 shall open to allow cleaning only in the direction of flow. [Initial comment: An approved 2-way cleanout fitting is allowed to be used at the junction of a building drain and a building sewer; otherwise, cleanouts shall open to allow cleaning only in the direction of flow (see “TWO-WAY CO #6”, UT01 and P1.1). Reference: Section 708.1.8, IPC 2018.] | ||
| 02/10/2025 | Fire New Construction | REQUIRES RESUBMIT | -Could not locate the information to my previous comments. See original comments below. -Could not locate the door/gate hardware information. -Also could not locate the exiting plan from the pool deck that has an OL of 300. -Specify the type of lockset with part number (panic hardware) on the exit gates. Include gate G104. There should be a door schedule included. -Include pool deck in the safety floor plan, Sheet A1.1, with exiting from pool deck. Show all required exits, with exiting travel distance to a public way. john.vincent@tucsonaz.gov 5203495581 |
||
| 01/28/2025 | PDSD Application Completeness Express | REVIEW COMPLETED |