Permit Number: TC-COM-0424-00665
Parcel: 13801001D

Address:
6100 S 12TH AV

Review Status: Requires Resubmit

Review Details: COMMERCIAL REVIEW - FULL v.3

Permit Number - TC-COM-0424-00665
Review Name: COMMERCIAL REVIEW - FULL v.3
Review Status: Requires Resubmit
Review Date Reviewer's Name Type of Review Description Status Comments
01/30/2025 Commercial Electrical APPROVED
02/06/2025 Commercial Mechanical APPROVED
02/10/2025 Bldg Permits - Post Review Express PENDING ASSIGNMENT
02/06/2025 Commercial Plumbing REQUIRES RESUBMIT Comment not addressed. Cleanout #6 on sheet UT01 and sheet P1.1 shall open to allow cleaning only in the direction of flow. [Initial comment: An approved 2-way cleanout fitting is allowed to be used at the junction of a building drain and a building sewer; otherwise, cleanouts shall open to allow cleaning only in the direction of flow (see “TWO-WAY CO #6”, UT01 and P1.1). Reference: Section 708.1.8, IPC 2018.]
02/10/2025 Fire New Construction REQUIRES RESUBMIT -Could not locate the information to my previous comments. See original comments below.
-Could not locate the door/gate hardware information.
-Also could not locate the exiting plan from the pool deck that has an OL of 300.

-Specify the type of lockset with part number (panic hardware) on the exit gates. Include gate G104. There should be a door schedule included. -Include pool deck in the safety floor plan, Sheet A1.1, with exiting from pool deck. Show all required exits, with exiting travel distance to a public way. john.vincent@tucsonaz.gov 5203495581
01/28/2025 PDSD Application Completeness Express REVIEW COMPLETED