Permit Number: TC-COM-0424-00665
Parcel: 13801001D

Address:
6100 S 12TH AV

Review Status: Requires Resubmit

Review Details: COMMERCIAL REVIEW - FULL v.2

Permit Number - TC-COM-0424-00665
Review Name: COMMERCIAL REVIEW - FULL v.2
Review Status: Requires Resubmit
Review Date Reviewer's Name Type of Review Description Status Comments
12/05/2024 Bldg Permits - Post Review Express PENDING ASSIGNMENT
11/25/2024 Commercial Electrical REQUIRES RESUBMIT Please address the electrical plan review comments and provide a written response. Provide evidence on the plans that the proposed exterior lighting fully complies with the Outdoor Lighting Code. See section 104 for plan submittal requirements.

SECOND REVIEW: Above comment did not appear to be fully addressed. Please address comment with next submittal.

1. Provide site lighting plans with the following information on the plans; (a) Provide a complete luminaire schedule. (b) Full compliance with sections 104.2.1(1), (2), (3).
1. SECOND REVIEW: Above comment did not appear to be addressed. Please address comment with next submittal. Please provide a site lighting plan in compliance with the information requested above.

2. See table 401.1, Include PARCEL SIZE, LIGHTING AREA and OPTION utilized per table 401.1, and indicate this information in the lighting site plan.
2. SECOND REVIEW: Above comment did not appear to be addressed. Please address comment with next submittal. Please Include PARCEL SIZE, LIGHTING AREA and OPTION utilized per table 401.1, and indicate this information in the lighting site plan
3. 402.1 (light source color temperature requirements), shielding requirements, etc .
3. SECOND REVIEW: Above comment did not appear to be fully addressed. Please address comment with next submittal. Although the maximum color temperature was identified at 3500K, the shielding information was not provided. Please provide the balance of the information, for the site lighting plan per the information requested above.

4. Provide calcs for total lumens allowed and total lumens proposed per acre for Full Cut Off and Unshielded per table 401.1. Must include existing to remain lighting.
4. SECOND REVIEW: Above comment did not appear to be addressed. Please address comment and provide the Outdoor Lighting Calculations as described above, with next submittal.

5. Indicate whether or not a special inspection is required per sec. 104.2.2, and 106.2.

5. SECOND REVIEW: Above comment did not appear to be addressed. Please address the comment above and indicate whether or not a special inspection is required as described above, with next submittal.


6. Specify any exceptions used.

6. SECOND REVIEW: Above comment did not appear to be addressed.
Please address the comment above and specify any exceptions used.

7. Provide Curfew lighting controls If applicable Per section 403.

7. SECOND REVIEW: Above comment did not appear to be addressed.
Please address the comment above and provide Curfew lighting controls If applicable Per section 403.


8. Provide complete compliance with the 2018 IECC for the interior and exterior lighting where applicable. Do not confuse the Outdoor Lighting Code with the IECC.

8. SECOND REVIEW: Above comment did not appear to be fully addressed.
The 2018 ICC interior lighting compliance was provided; however, exterior lighting compliance was not provided. Please provide evidence that the exterior lighting complies with the 2018 IECC.

Ref; 2017 NEC, 2012 Tucson/Pima County Outdoor Lighting Code (OLC), 2018 IBC sec 107.2.1. 2018 IECC.
2. Demonstrate energy code compliance for the building envelope using calculations based on the current code. Reference: Sections C101.5, C103.2, C303, and C401.2, International Energy Conservation Code 2018.


Please contact me if you have any questions about these comments.
Mark Masek
Plans Examiner – Building Safety
Planning and Development Services | City of Tucson
main 520.837.4994
email mark.masek@tucsonaz.gov
11/25/2024 Commercial Mechanical REQUIRES RESUBMIT Please submit your revised documents and provide a letter with a written response letter addressing each of the comments indicating how the Mechanical Review comments were resolved. Additionally, please submit complete copies of all permit documents (i.e. plans, calculations, reports, etc.) even if they have not been changed.

2. Demonstrate energy code compliance for the building envelope using calculations based on the current code. Reference: Sections C101.5, C103.2, C303, and C401.2, International Energy Conservation Code 2018.

2. SECOND REVIEW: Above comment did not appear to be addressed. Please address comment with next submittal.

3. Show how one of the “Additional Efficiency Package Options” (C406, IECC 2018) is to be accomplished. Reference: Section C401.2, IECC 2018.

3. SECOND REVIEW: Above comment did not appear to be addressed. Please address comment with next submittal.

4. Provide heating and cooling load calculations to justify the heating/cooling capacities of FC-1/HPCU-1. Reference: Section C403.1.1 and C403.3.1, IECC 2018.

4. SECOND REVIEW: Above comment did not appear to be addressed. Please address comment with next submittal.

Please contact me if you have any questions about these comments.
Mark Masek
Plans Examiner – Building Safety
Planning and Development Services | City of Tucson
main 520.837.4994
email mark.masek@tucsonaz.gov
11/25/2024 Commercial Plumbing REQUIRES RESUBMIT Please submit your revised documents and provide a letter with a written response letter addressing each of the comments indicating how the Plumbing Review comments were resolved. Additionally, please submit complete copies of all permit documents (i.e. plans, calculations, reports, etc.) even if they have not been changed.

4. An approved 2-way cleanout fitting is allowed to be used at the junction of a building drain and a building sewer; otherwise, cleanouts shall open to allow cleaning only in the direction of flow (see “TWO-WAY CO #6”, UT01 and P1.1). Reference: Section 708.1.8, IPC 2018.

4. SECOND REVIEW: This comment partially remains and is expanded: For consistency, please coordinate the location of the TWO-WAY CO #6”, UT01 and P1.1to show the same location on both drawings. IBC 107.2.1

6. The Equipment Room shows floor drains, emergency shower/eyewash, and water supply requirements “PER MEP” but no drawings depict any water supply or a building sewer to the building. How will this building be included in this activity?

6. SECOND REVIEW: This comment partially remains and is expanded: The Plumbing Fixture Schedule now includes the Emergency Shower/Eye Wash and Floor drain.
a. The civil drawings (Sheet UT01), do not show water supply or building sewer to the building. Amend the civil plans to show continuation and point of connection to site water and sewer. IBC 107.2.1
b. The Emergency Shower/Eye wash and Floor drain Plumbing Plan is inaccurately identified as Fire Sprinkler Equipment Plan on (Sheet P2.1). Amend plans to provide an accurate identifier and complete the reference callouts for the drawing detail. IBC 107.2.1
c. Amend plans to provide Soil & Vent Riser and CW & HW Riser drawings depicting the Emergency Shower/Eye wash and Floor drain system. IBC 107.2.1

Please contact me if you have any questions about these comments.
Mark Masek
Plans Examiner – Building Safety
Planning and Development Services | City of Tucson
main 520.837.4994
email mark.masek@tucsonaz.gov
12/05/2024 Fire New Construction REQUIRES RESUBMIT -Please include a response letter addressing fire comments.
john.vincent@tucsonaz.gov
5203495581
11/22/2024 PDSD Application Completeness Express REVIEW COMPLETED