Permit Review Detail
Review Status: Requires Resubmit
Review Details: COMMERCIAL REVIEW - FULL v.1
Permit Number - TC-COM-0424-00664
Review Name: COMMERCIAL REVIEW - FULL v.1
Review Status: Requires Resubmit
| Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
|---|---|---|---|---|---|
| 12/11/2024 | Bldg Permits - Post Review Express | PENDING ASSIGNMENT | |||
| 12/11/2024 | Commercial Electrical | REQUIRES RESUBMIT | Please address the electrical plan review comments and provide written response. 1 The electrical plan submitted shows an 800 amp service required per the load calculations. Please revise the load calculations to correlate with the revised 200 amp service. REF; 2018 IBC section 107.2.1, 2017 NEC |
||
| 12/11/2024 | PDSD Application Completeness Express | REVIEW COMPLETED |