Permit Review Detail
Review Status: Requires Resubmit
Review Details: COMMERCIAL REVIEW - LIMITED v.4
Permit Number - TC-COM-0424-00664
Review Name: COMMERCIAL REVIEW - LIMITED v.4
Review Status: Requires Resubmit
| Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
|---|---|---|---|---|---|
| 08/19/2024 | Commercial Building | APPROVED | |||
| 08/19/2024 | Commercial Electrical | APPROVED | |||
| 08/28/2024 | Commercial Plumbing | APPROVED | |||
| 08/28/2024 | Bldg Permits - Post Review Express | PENDING ASSIGNMENT | |||
| 08/28/2024 | Commercial Mechanical | REQUIRES RESUBMIT | The Total Building Summary Loads shows 495 CFM of summer ventilation used to calculate the cooling load for the AC unit. The actual ventilation airflow rate is 77 CFM, about one-sixth of the flow rate used in the calculation. Recalculate the cooling load for the AC unit. [Third comment: The heating/cooling load must be recalculated using the corrected ventilation airflow rates.] [Second comment: Clarify the ventilation being supplied to the area served by the heat pump. The equipment schedule shows 719 CFM, the Outside Air Ventilation Schedule shows 77 CFM and the heating/cooling load calculations list 330 CFM in the winter and 825 CFM in the summer. In addition, the 4-ton unit is scheduled to deliver 1600 CFM but only 825 CFM is identified on the Mechanical Plan.] [Initial comment: Provide heating and cooling load calculations to justify the heating/cooling capacities of the specified HVAC units. Reference: Section C403.1.1 and C403.3.1, IECC 2018.] | ||
| 08/15/2024 | PDSD Application Completeness Express | REVIEW COMPLETED |