Permit Number: TC-COM-0424-00611
Parcel: 11519004R

Review Status: Requires Resubmit

Review Details: COMMERCIAL REVIEW - FULL REVISION v.1

Permit Number - TC-COM-0424-00611
Review Name: COMMERCIAL REVIEW - FULL REVISION v.1
Review Status: Requires Resubmit
Review Date Reviewer's Name Type of Review Description Status Comments
12/31/2024 Bldg Permits - Post Review Express PENDING ASSIGNMENT
12/31/2024 Commercial Electrical REQUIRES RESUBMIT Permit Review TC-COM-0424-00611 (2094 N DRAGOON ST TUCSON, AZ 85745)
Plan review for the above referenced structure has been completed. This letter reflects comments to be addressed. Provide updated Plans/calculations and a written response Letter to each of the notated items indicating action taken. Resubmitted plans that do not contain a written response Letter addressing each of the notated items indicating action taken, may be delayed until response letter is received.
Code reference, 2018 International Building Code (IBC), 2017 National Electrical Code (NEC).
Outdoor Lighting Code (OLC).

1. Please provide the specification sheets for the new connectors being used.
2. Add a note, with revision clouded on the appropriate sheets showing the connector being used. The updated plans have removed the old supply-side connection note, but no updated note was added (sheet E2). IBC section 107.1, NEC 90.4.

Contact Jeremy Hamblin with any questions: Jeremy.hamblin@tucsonaz.gov