Permit Number: TC-COM-0424-00570
Parcel: 14041124E

Review Status: Requires Resubmit

Review Details: COMMERCIAL PDSD SIMPLE REVIEW v.3

Permit Number - TC-COM-0424-00570
Review Name: COMMERCIAL PDSD SIMPLE REVIEW v.3
Review Status: Requires Resubmit
Review Date Reviewer's Name Type of Review Description Status Comments
05/10/2024 Bldg Permits - Post Review PENDING ASSIGNMENT
05/10/2024 External Reviewers - SAFEBuilt REQUIRES RESUBMIT Structural N/A

Building N/A

Mechanical N/A

Electrical(E) Reviewer
Ron Ross
rross@safebuilt.com
Denied
Reason:
Date Completed : 5/9/2024 7:55:50 AM
For future information, comment only: Electrical designs of 400 amp and larger are required to be signed and sealed by a licensed electrical engineer.

Missing sheets require confirmation that the sheets are removed from the set or need to be submitted for review.

Duplicated numbered sheets shall be renumbered/renamed.

Comments for CP100
1. For sheet 2023-4104-051: 37.5 KVA Transformer secondary conductors are undersized for a 1 phase transformer. Primary is also undersized, but the primary conductors are protected properly with the 50-amp CB. The secondary conductors need to can carry 100 amps continuously if using the undersized 50-amp CB on the primary. Undersized circuit breakers can nuisance trip on transformers due to inrush currents, but this is not a code violation. Sheet 2023-4104-101 confirms this is a 37.5 KVA transformer (unreadable information), but Sheet 2023-4104-112 shows a 30
KVA 3 phase transformer with different (and code compliant) conductor sizes with acceptable overcurrent protection. Coordinate if same transformer. Correct code deficiencies and wiring detail if 37.5 KVA transformer.

2. For sheet 2023-4104-109: Terminal Block and #10 AWG conductors of the main feeder will be overloaded when all four 7.5 Hp motors are able to run. There is no overload protection on the common feed (#10 AWG which is undersized) to all 7.5 Hp motors.

3. For sheet 2023-4104-111: Missing from set

4. For sheet 2023-4104-114A: Cannot determine NEC overcurrent protection compliance for any receptacles shown ie size of conductors not called out.

5. For sheet 2023-4104-114A: Duplicated sheet number for two different sheets. Also, cannot determine NEC overcurrent protection compliance for any receptacles shown ie size of conductors not called out.

6. For sheet 2023-4104-118A: Missing from set.

◦ Comments for CP200

7. For sheet 2023-4104-104/2: duplicate sheet number, two different sheets. No electrical issues

8. For sheet 2023-4104-109: 5 Hp Motor MOT100.1107 has wrong FLA of 47.6 amps. FLAs are not shown for right side column of motors.

9. For sheet 2023-4104-111: Missing from set

10. For sheet 2023-4104-113: Duplicate sheet number for three different sheets. No electrical issues.

11. For sheet 2023-4104-113: Duplicate sheet number for three different sheets. No electrical issues.

12. For sheet 2023-4104-114A: Cannot determine NEC overcurrent protection compliance for the receptacles shown ie size of conductors not called out.

13. For sheet 2023-4104-114A: Duplicated sheet number for two different sheets. No electrical issues

14. For sheet 2023-4104-126: Missing from set

15. For sheet 2023-4104-138: Missing from set

Plumbing N/A
04/26/2024 PDSD Application Completeness REVIEW COMPLETED