Permit Number: TC-COM-0423-01148
Parcel: 134234120

Address:
203 S WILMOT RD

Review Status: Requires Resubmit

Review Details: COMMERCIAL REVIEW - FULL v.3

Permit Number - TC-COM-0423-01148
Review Name: COMMERCIAL REVIEW - FULL v.3
Review Status: Requires Resubmit
Review Date Reviewer's Name Type of Review Description Status Comments
07/03/2023 External Reviewers - SAFEBuilt APPROVED Activity Number: TC-COM-0423-01148

GENERAL:
Provide written responses to all review comments.
Provide a complete plan set.
Provide additional documents as requested by review staff.

Structural(S) Reviewer
Daljit Benipal
dbenipal@safebuilt.com
Conditionally Approved
Reason:
Date Completed : 6/14/2023 10:14:02 AM
NOTE: Every effort has been made to identify the code violations. Any oversight by the review team shall not be considered an authority to violate, set aside, cancel or alter applicable codes or ordinances. The plan review and permit issuance shall not be considered a warranty or guarantee. The Structural Engineer is responsible for following ALL applicable Federal, State and local Municipal Codes and Ordinances.


Building(B) Reviewer
Andrew Bevis
abevis@safebuilt.com
Approved
Reason:
Date Completed : 6/12/2023 3:54:02 PM


Mechanical(M) Reviewer
Neil Samaan
nsamaan@safebuilt.com
Conditionally Approved
Reason:
Date Completed : 6/9/2023 11:45:02 PM
. Provide appliance duty classification for hood 3 sheet H5.1 (IMC2018,507.2.1) Complied
2. You are exhausting 2095 cfm through hood 1 but only bringing in 1,446 cfm through the perforated supply plenum, you must bring in approximately the same amount of air that you exhaust this is the same for all 3 hoods sheet H5.1 (IMC208,508.1) Complied
3. Make note on schedule that the kitchen exhaust for the hoods shall be interlocked with the make up air unit on sheet H5.1 (IMC 2018,508.1) Complied
4. Both walk in coolers condensing units shall be on schedule with all pertinent information including the amount and type of refrigerant along with the model and serial #'s. votages, amps, etc. (IMC2018,106.3.1) Complied
Approved/subject to field approval


Electrical(E) Reviewer
Matthew Payette
mpayette@safebuilt.com
Approved
Reason:
Date Completed : 5/20/2023 10:15:44 PM


Plumbing(P) Reviewer
Perry Hendershott
phendershott@safebuilt.com
Conditionally Approved
Reason:
Date Completed : 7/2/2023 10:53:34 PM
Third Plumbing Review:** OK Subject To Field Inspections
1).OK
2). OK
3). OK
4). OK
5). OK-Detail #7 on plan page P3.0 illustrates the water softener discharging to a drain, no drain is shown in that area on plan pages P1.U, P1.1 & P2.0. plan pages need to correlate - IPC 106.3.1 ** Subject To Field Inspections
6). OK
07/12/2023 Bldg Permits - Post Review PENDING ASSIGNMENT
07/12/2023 Site Engineering REQUIRES RESUBMIT Waiting on approval for TD-DEV-0423-00212

Scott Haseman
scott.haseman@tucsonaz.gov
07/06/2023 Site Zoning REQUIRES RESUBMIT FROM: PDSD Zoning Review Section

PROJECT: TC-COM-0423-01148
203 S; Wilmot Rd. – C-1
Food Service (3rd Review)

TRANSMITTAL DATE: July 06, 2023

COMMENTS: Please resubmit revised drawings along with a detailed response letter, which states how all Zoning Review Section comments were addressed.

This site is located in the C-1 zone (UDC 4.7.20). Food Service is a permitted use in this zone (Table 4.8-4), subject to Use Specific Standards 4.9.4.M.1 & 5 and 4.9.13.O.

1. Zoning has reviewed the building plans for compliance with Development Package (DP) TD-DEV-0423-00212 and although it appears that the plans match until the DP is approved by all review agencies Zoning cannot approve this building permit.

2. This comment was not addressed correctly. The DP sheets submitted in the building set are not the stamped approved DP sheets. There is no PDSD Approval stamp on any of the DP sheets. The development package sheets provided in the building plan set either need to be the stamped approved set, marked for reference only or removed from the set. If you elect to mark for reference only do not mark sheet C1.3 for reference only as it is reviewed for compliance by the plumbing review. If you elect to remove the plans from the set, do not remove sheet C1.3 as it is reviewed for compliance by the plumbing review.

If you have any questions about this transmittal, please contact Zone1.desk@tucsonaz.gov.
06/29/2023 PDSD Application Completeness REVIEW COMPLETED