Permit Number: TC-COM-0423-01148
Parcel: 134234120

Address:
203 S WILMOT RD

Review Status: Requires Resubmit

Review Details: COMMERCIAL REVIEW - FULL v.1

Permit Number - TC-COM-0423-01148
Review Name: COMMERCIAL REVIEW - FULL v.1
Review Status: Requires Resubmit
Review Date Reviewer's Name Type of Review Description Status Comments
05/23/2023 Bldg Permits - Post Review PENDING ASSIGNMENT
05/23/2023 External Reviewers - SAFEBuilt REQUIRES RESUBMIT Activity Number: TC-COM-0423-01148

GENERAL:
Provide written responses to all review comments.
Provide a complete plan set.
Provide additional documents as requested by review staff.

Structural(S) Reviewer
Daljit Benipal
dbenipal@safebuilt.com
Denied
Reason:
Date Completed : 5/22/2023 6:24:11 PM
1. Provide accurate information regarding Current Codes per International Building Code 2018. The information provided on sheet 12 of 100 as IBC 2012 is incorrect since State has adopted latest Codes.
2. Refer to Sheet 12 of 100 of the Structural Calculations and Structural Drawing S0.1. The Seismic Design Data parameters doesn’t match. Verify and make revisions as needed.
3. Refer to Structural Calculations sheet 14 of 100. This sheet calls for ASCE7-10, Revise calculations to ASCE7-16 and resubmit.
4. Refer to Structural Calculations sheet 18 of 100. This sheet calls for ASCE7-10, Revise calculations to ASCE7-16 and resubmit.
5. Provide Geotechnical Report for the proposed building per International Building Code 2018, Section 1803.1.
6. Submit documentation regarding implementation of Special Inspections and Testing program during construction to observe compliance with the Design Concepts and Specifications.
7. Provide schedule of special inspections as required in IBC Section 1705.
8. DEFERRED SUBMITTAL REQUIREMENTS
Structural general notes are to include any components of the building that may be considered deferred submittals.
IBC Section 107.3.4.1 requires deferred submittals to be approved by the building official.
If items will be deferred the plans are to clearly note the following per IBC Section 107.3.4.1:
* To be reviewed by design professional in responsible charge.
* Design professional shall affix a notation that the deferred items are in general conformance with their design of the building.
* They shall be submitted for review by the building official.
* Shall not be installed until approved by building official.
Submit a response letter addressing these correction items and provide bubbles on the revisions to the drawings.


Building(B) Reviewer
Andrew Bevis
abevis@safebuilt.com
Denied
Reason:
Date Completed : 5/16/2023 2:41:05 PM
1. Sheet T1.1: The occupant load calculation for the the dining room is incorrect. The IBC does not permit the usage of "actual" loads or chair counts beyond fixed seating. One must use the calculated load in determining further requirements. Provide the calculated loads using unconcentrated tables and chairs and any fixed seating (booths) and correlate any further requirements in accordance with Table 1004.5.
2. At least 5% of the dining surfaces are required to have mobility features. Provide calculations of the required amount of accessible seating and indicate the locations. Additionally, ensure that surfaces are properly dispersed throughout the structure. Section 226.1 and 226.2 of the 2010 ADAAG.


Mechanical(M) Reviewer
Neil Samaan
nsamaan@safebuilt.com
Denied
Reason:
Date Completed : 5/9/2023 10:35:36 PM
1. Provide appliance duty classification for hood 3 sheet H5.1 (IMC2018,507.2.1)
2. You are exhausting 2095 cfm through hood 1 but only bringing in 1,446 cfm through the perforated supply plenum, you must bring in approximately the same amount of air that you exhaust this is the same for all 3 hoods sheet H5.1 (IMC208,508.1)
3. Make note on schedule that the kitchen exhaust for the hoods shall be interlocked with the make up air unit on sheet H5.1 (IMC 2018,508.1)
4. Both walk in coolers condensing units shall be on schedule with all pertinent information including the amount and type of refrigerant along with the model and serial #'s. votages, amps, etc. (IMC2018,106.3.1)


Electrical(E) Reviewer
Matthew Payette
mpayette@safebuilt.com
Approved
Reason:
Date Completed : 5/20/2023 10:15:44 PM


Plumbing(P) Reviewer
Perry Hendershott
phendershott@safebuilt.com
Denied
Reason:
Date Completed : 5/20/2023 7:33:41 PM
First Plumbing Review:
1). Roofs A & C on plan page A1.2 need secondary drains -IPC 1106.5. 1108
2). Plan page P1.U needs to include continuation of grease line to grease interceptor, & outlet continuation of grease interceptor outlet to sewer connection. ( Also not shown on C1.3 utility plan) -IPC 106.3.1, IPC 1003.1
3). Plan page P1.U needs to include grease interceptor size & calculations- Tucson Plumbing Code amendments
4). Grease interceptor will need to be vented - IPC 1003.9
5). Detail #7 on plan page P3.0 illustrates the water softener discharging to a hub drain, no hub drain is shown in that area on plan pages P1.U, P1.1 & P2.0. plan pages need to correlate - IPC 106.3.1
6). plan page A1.2 shows new roof drains, the plumbing plans need to illustrate the roof drain conductors & sizing calculations. -IPC 106.3.1, 1106.1, 1106.2
05/22/2023 Site Engineering REQUIRES RESUBMIT See Zoning Comment
05/15/2023 Site Zoning REQUIRES RESUBMIT FROM: PDSD Zoning Review Section

PROJECT: TC-COM-0423-01148
203 S; Wilmot Rd. – C-1
Food Service (1st Review)

TRANSMITTAL DATE: May 15, 2023

COMMENTS: Please resubmit revised drawings along with a detailed response letter, which states how all Zoning Review Section comments were addressed.

This site is located in the C-1 zone (UDC 4.7.20). Food Service is a permitted use in this zone (Table 4.8-4), subject to Use Specific Standards 4.9.4.M.1 & 5 and 4.9.13.O.

1. Zoning has reviewed the building plans for compliance with Development Package (DP) TD-DEV-0423-00212 and although it appears that the plans match until the DP is approved by all review agencies Zoning cannot approve this building permit.

If you have any questions about this transmittal, please contact Zone1.desk@tucsonaz.gov.
05/05/2023 Fire New Construction REVIEW COMPLETED
05/03/2023 PDSD Application Completeness REVIEW COMPLETED