Permit Review Detail
Review Status: Requires Resubmit
Review Details: COMMERCIAL REVIEW - FULL v.4
Permit Number - TC-COM-0423-01074
Review Name: COMMERCIAL REVIEW - FULL v.4
Review Status: Requires Resubmit
| Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
|---|---|---|---|---|---|
| 08/15/2023 | Commercial Electrical | REQUIRES RESUBMIT | Please address the electrical plan review comments and provide a written response. The electrical plan review comments were not completely addressed or the response was not detailed enough to satisfy the review comment. 1 Response to previous Electrical review comment #1; The Photometric Analysis shows the new under canopy luminaires Color Temperature rated at 4000K. This is in violation of the 2012 City of Tucson Outdoor Lighting Code (OLC) section 402.1, (3500K max). To verify OLC compliance, provide the information required on the site lighting plans, per section 104.2 (Plan/Permit Submittal Requirements), and Lumen calculations per 104.2.1, 104.2.3, OLC. Provide Luminaires manufacturers cut sheet with all specifications highlighted or encircled. Be advised, Under Canopy luminaires that provide full cut-off shielding by the manufacturer, and lamp color temperature output of 3500K or less is exempt from the lumen calculations requirement per exception 104.2.1. 2 The revised PV plans were not re-submitted, only the photometric lighting plan. Be sure to address all the previous plan review comments and revise the plans as necessary. . The required plans, descriptions and data shall be sufficiently complete to enable the plans examiner to readily determine compliance with the requirements of all applicable Codes. Ref; 2018 IBC section 107.2.1, 2017 NEC, 2012 City of Tucson Outdoor Lighting Code. |
||
| 07/25/2023 | Site Engineering | REQUIRES RESUBMIT | See zoning comment | ||
| 07/20/2023 | Site Zoning | REQUIRES RESUBMIT | FROM: Paul Camarena PDSD Zoning Review Section PROJECT TC-COM-0423-01074 3939 N ORACLE RD Zoning C-2 TRANSMITTAL DATE:‎July 20, 2023 COMMENTS: Please resubmit revised drawings along with a detailed response letter, which states how all Zoning Review Section comments were addressed. 1.COMMENT: No plan set was provided, Please submit a plan set, If you have any questions about this transmittal, Contact Paul Camarena at (520)837-4986 or by email Paul.Camarena@tucsonaz.gov |
||
| 07/20/2023 | PDSD Application Completeness Express | REVIEW COMPLETED |