Permit Review Detail
Review Status: Requires Resubmit
Review Details: COMMERCIAL REVIEW - FULL v.7
Permit Number - TC-COM-0423-01074
Review Name: COMMERCIAL REVIEW - FULL v.7
Review Status: Requires Resubmit
| Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
|---|---|---|---|---|---|
| 05/08/2024 | Bldg Permits - Post Review Express | PENDING ASSIGNMENT | |||
| 05/08/2024 | Commercial Electrical | REQUIRES RESUBMIT | Please address the electrical plan review comments and provide a written response. 1 Ref; Electric Line diagrams. What happened to note #11? 2 Provide for a field evaluation to be performed after the line side PV Interconnection is preformed. Inspection and approval by a NRTL agency. This to re-certify the listing of the Electrical Service Equipment. Indicate this on the electrical line diagram plans. NEC 110.3 and 230.66. Ref; 2018 IBC section 107.2.1, 2017 NEC. |
||
| 04/09/2024 | PDSD Application Completeness Express | REVIEW COMPLETED |