Permit Review Detail
Review Status: Requires Resubmit
Review Details: COMMERCIAL REVIEW - FULL v.2
Permit Number - TC-COM-0423-01074
Review Name: COMMERCIAL REVIEW - FULL v.2
Review Status: Requires Resubmit
| Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
|---|---|---|---|---|---|
| 06/20/2023 | Commercial Building | APPROVED | |||
| 06/21/2023 | Bldg Permits - Post Review Express | PENDING ASSIGNMENT | |||
| 06/21/2023 | Commercial Electrical | REQUIRES RESUBMIT | Please address the electrical plan review comments and provide a written response. 1 Provide complete compliance with the City of Tucson Outdoor Lighting Code For the under-Canopy lighting. See section 401.2.1(2). Comply with light source color temperature output and shielding requirements. 2 Provide a detailed description including hardware, how the supply side PV Interconnection is not going to compromise the listing of the Service Equipment. The option would be to provide a field evaluation by an NRTL agency to re- establish the listing of the equipment after the proposed interconnection is performed. Wouldn’t it be easier to tie into the CT cabinet? 3 Provide complete grounding details for the PV Racking and Grounding Electrode system at the PV Array’s per NEC art 690.47. 4 Verify that the DG Utility disconnect is rated suitable for use as service equipment per NEC 690.13(C) Ref; 2018 IBC section 107.2.1, 2017 NEC, 2012 City of Tucson Outdoor Lighting Code. |
||
| 05/31/2023 | Site Engineering | REQUIRES RESUBMIT | 1. The locations of the carports in theCONS plans provided in the submittal do not match the approved locations of the carports in development package DP22-0094. Locations must match those in the approved development package. Lianne Evans lianne.evans@tucsonaz.gov |
||
| 05/31/2023 | Site Zoning | REQUIRES RESUBMIT | ZONING REVIEW TRANSMITTAL FROM: PDSD Zoning Review PROJECT: TC-COM-0423-01074 3939 N. Oracle Rd. – C-2 Covered Parking Structures (1st Review) TRANSMITTAL: May 31, 2023 Please resubmit revised drawings and any redlined plans along with a detailed response letter, which states how all Zoning Review Section comments were addressed. This site is located in C-2 zone (UDC 4.7.21). Financial Service is an allowed use in zone (UDC Table 4.8-4), subject to Use Specific Standards 4.9.4.L.3, 4.9.13.E, and 4.9.13.P. 1. The proposed location for the proposed covered parking structures does not match the locations show on approved DP22-0094. A revision to the DP is required. If you have any questions about this transmittal, please contact Zone1.desk@tucsonaz.gov. |
||
| 05/26/2023 | Fire New Construction | REVIEW COMPLETED | |||
| 05/22/2023 | PDSD Application Completeness Express | REVIEW COMPLETED |