Permit Number: TC-COM-0423-01074
Parcel: 10605001C

Address:
3939 N ORACLE RD

Review Status: Requires Resubmit

Review Details: COMMERCIAL REVIEW - FULL v.2

Permit Number - TC-COM-0423-01074
Review Name: COMMERCIAL REVIEW - FULL v.2
Review Status: Requires Resubmit
Review Date Reviewer's Name Type of Review Description Status Comments
06/20/2023 Commercial Building APPROVED
06/21/2023 Bldg Permits - Post Review Express PENDING ASSIGNMENT
06/21/2023 Commercial Electrical REQUIRES RESUBMIT Please address the electrical plan review comments and provide a written response.

1 Provide complete compliance with the City of Tucson Outdoor Lighting Code For the under-Canopy lighting. See section 401.2.1(2). Comply with light source color temperature output and shielding requirements.

2 Provide a detailed description including hardware, how the supply side PV Interconnection is not going to compromise the listing of the Service Equipment. The option would be to provide a field evaluation by an NRTL agency to re- establish the listing of the equipment after the proposed interconnection is performed. Wouldn’t it be easier to tie into the CT cabinet?

3 Provide complete grounding details for the PV Racking and Grounding Electrode system at the PV Array’s per NEC art 690.47.

4 Verify that the DG Utility disconnect is rated suitable for use as service equipment per NEC 690.13(C)

Ref; 2018 IBC section 107.2.1, 2017 NEC, 2012 City of Tucson Outdoor Lighting Code.
05/31/2023 Site Engineering REQUIRES RESUBMIT 1. The locations of the carports in theCONS plans provided in the submittal do not match the approved locations of the carports in development package DP22-0094. Locations must match those in the approved development package.

Lianne Evans
lianne.evans@tucsonaz.gov
05/31/2023 Site Zoning REQUIRES RESUBMIT ZONING REVIEW TRANSMITTAL

FROM: PDSD Zoning Review

PROJECT:
TC-COM-0423-01074
3939 N. Oracle Rd. – C-2
Covered Parking Structures (1st Review)

TRANSMITTAL: May 31, 2023

Please resubmit revised drawings and any redlined plans along with a detailed response letter, which states how all Zoning Review Section comments were addressed.

This site is located in C-2 zone (UDC 4.7.21). Financial Service is an allowed use in zone (UDC Table 4.8-4), subject to Use Specific Standards 4.9.4.L.3, 4.9.13.E, and 4.9.13.P.

1. The proposed location for the proposed covered parking structures does not match the locations show on approved DP22-0094. A revision to the DP is required.

If you have any questions about this transmittal, please contact Zone1.desk@tucsonaz.gov.
05/26/2023 Fire New Construction REVIEW COMPLETED
05/22/2023 PDSD Application Completeness Express REVIEW COMPLETED