Permit Number: TC-COM-0423-01046
Parcel: 10703146A

Review Status: Requires Resubmit

Review Details: COMMERCIAL REVIEW - FULL v.2

Permit Number - TC-COM-0423-01046
Review Name: COMMERCIAL REVIEW - FULL v.2
Review Status: Requires Resubmit
Review Date Reviewer's Name Type of Review Description Status Comments
07/17/2023 Bldg Permits - Post Review Express PENDING ASSIGNMENT
07/17/2023 Commercial Electrical REQUIRES RESUBMIT Please address the electrical comments and provide a written response.

All Electrical and Architectual plan sheets must be sealed by a Registrant registered in the State of Arizona including the Site Plan.

Provide a Conduit Conductor schedule for the feeders shown on the electrical line diagrams.

The Office Equipment View elevation drawing does not show the Laser PV array electrical equipment. Please show this equipment.

Ref; 2018 IBC section 107.1, 107.2.1, 2017 NEC.
06/12/2023 PDSD Application Completeness Express REVIEW COMPLETED