Review Status: Requires Resubmit
Review Details: COMMERCIAL REVIEW - FULL v.2
Permit Number - TC-COM-0423-01046
Review Name: COMMERCIAL REVIEW - FULL v.2
Review Status: Requires Resubmit
| Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
|---|---|---|---|---|---|
| 07/17/2023 | Bldg Permits - Post Review Express | PENDING ASSIGNMENT | |||
| 07/17/2023 | Commercial Electrical | REQUIRES RESUBMIT | Please address the electrical comments and provide a written response. All Electrical and Architectual plan sheets must be sealed by a Registrant registered in the State of Arizona including the Site Plan. Provide a Conduit Conductor schedule for the feeders shown on the electrical line diagrams. The Office Equipment View elevation drawing does not show the Laser PV array electrical equipment. Please show this equipment. Ref; 2018 IBC section 107.1, 107.2.1, 2017 NEC. |
||