Microfiche records prior to 2006 have not been completely digitized and may not be available yet on PRO. If you can not find what you are looking for please submit a records request.
Permit Review Detail
Review Status: Requires Resubmit
Review Details: COMMERCIAL REVIEW - FULL v.1
Permit Number - TC-COM-0423-01045
Review Name: COMMERCIAL REVIEW - FULL v.1
Review Status: Requires Resubmit
| Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
|---|---|---|---|---|---|
| 04/29/2024 | Bldg Permits - Post Review Express | PENDING ASSIGNMENT | |||
| 04/29/2024 | Commercial Electrical | REQUIRES RESUBMIT | Please address the electrical plan review comments and provide a written response 1 Indicate the locations on the roof of the Sun Volt RSD contactors in order to verify compliance for PV module-controlled conductor array boundaries, NEC 690.12(A)(B)&(C). Ref; 2018 IBC section 107.2.1, 2017 NEC. |
||
| 03/25/2024 | PDSD Application Completeness Express | REVIEW COMPLETED |