Microfiche records prior to 2006 have not been completely digitized and may not be available yet on PRO. If you can not find what you are looking for please submit a records request.

Permit Number: TC-COM-0423-01044
Parcel: 10703146A

Review Status: Requires Resubmit

Review Details: COMMERCIAL REVIEW - FULL v.3

Permit Number - TC-COM-0423-01044
Review Name: COMMERCIAL REVIEW - FULL v.3
Review Status: Requires Resubmit
Review Date Reviewer's Name Type of Review Description Status Comments
07/17/2023 Bldg Permits - Post Review Express PENDING ASSIGNMENT
07/17/2023 Commercial Electrical REQUIRES RESUBMIT Please address the electrical comments and provide a written response.

The Office PV system mounted on the Industrial Building roof must be grounded to the Industrial Buildings Grounding Electrode system per NEC art 690..47.

Because this Building supports ‘Multiple PV systems’, provide a Directory in accordance with NEC art 609.4, 705.10 identifying each system.

Verify the amount of PV Modules installed on the roof of the Industrial building that are assigned to the Office Building. Plan sheet A-01 and A-02 show 256 PV Modules and the actual roof count shown in maroon font is 260. Please clarify.

All Electrical and Architectural plan sheets must be sealed by a Registrant registered in the State of Arizona including the Site Plan.

Ref; 2018 IBC section 107.1, 107.2.1, 2017 NEC.
06/12/2023 PDSD Application Completeness Express REVIEW COMPLETED