Permit Review Detail
Review Status: Requires Resubmit
Review Details: COMMERCIAL REVIEW - FULL v.3
Permit Number - TC-COM-0423-01044
Review Name: COMMERCIAL REVIEW - FULL v.3
Review Status: Requires Resubmit
| Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
|---|---|---|---|---|---|
| 07/17/2023 | Bldg Permits - Post Review Express | PENDING ASSIGNMENT | |||
| 07/17/2023 | Commercial Electrical | REQUIRES RESUBMIT | Please address the electrical comments and provide a written response. The Office PV system mounted on the Industrial Building roof must be grounded to the Industrial Buildings Grounding Electrode system per NEC art 690..47. Because this Building supports ‘Multiple PV systems’, provide a Directory in accordance with NEC art 609.4, 705.10 identifying each system. Verify the amount of PV Modules installed on the roof of the Industrial building that are assigned to the Office Building. Plan sheet A-01 and A-02 show 256 PV Modules and the actual roof count shown in maroon font is 260. Please clarify. All Electrical and Architectural plan sheets must be sealed by a Registrant registered in the State of Arizona including the Site Plan. Ref; 2018 IBC section 107.1, 107.2.1, 2017 NEC. |
||
| 06/12/2023 | PDSD Application Completeness Express | REVIEW COMPLETED |