Permit Number: TC-COM-0423-01042
Parcel: 105102450

Review Status: Requires Resubmit

Review Details: COMMERCIAL PDSD SIMPLE REVIEW v.1

Permit Number - TC-COM-0423-01042
Review Name: COMMERCIAL PDSD SIMPLE REVIEW v.1
Review Status: Requires Resubmit
Review Date Reviewer's Name Type of Review Description Status Comments
05/11/2023 Bldg Permits - Post Review PENDING ASSIGNMENT
05/11/2023 Commercial Mechanical REQUIRES RESUBMIT 1. Provide an auxiliary or secondary condensate drain system for the proposed heat pump indoor unit. Reference: Section 307.2.3, IMC 2018.
2. Clarify the purpose of a condensate drain for the proposed outdoor unit for the heat pump. Reference: Section 304.1, IMC 2018.
04/13/2023 PDSD Application Completeness REVIEW COMPLETED