Permit Review Detail
Review Status: Requires Resubmit
Review Details: BUILDING DEFERRED SUBMITTAL REVIEW v.1
Permit Number - TC-COM-0423-00982
Review Name: BUILDING DEFERRED SUBMITTAL REVIEW v.1
Review Status: Requires Resubmit
Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
---|---|---|---|---|---|
07/17/2024 | Bldg Permits - Post Review | PENDING ASSIGNMENT | |||
07/17/2024 | Air Balancing/Commissioning Report (Deferred Submittal) | REQUIRES RESUBMIT | The air balance report shows that the Type I kitchen hood is not performing as designed. Take corrective action and resubmit the air balance report. | ||
07/16/2024 | PDSD Application Completeness | REVIEW COMPLETED |