Permit Number: TC-COM-0423-00974
Parcel: 141367940

Review Status: Requires Resubmit

Review Details: COMMERCIAL REVIEW - FULL v.1

Permit Number - TC-COM-0423-00974
Review Name: COMMERCIAL REVIEW - FULL v.1
Review Status: Requires Resubmit
Review Date Reviewer's Name Type of Review Description Status Comments
05/12/2023 Site Engineering APPROVED SPECS SPECIFIC TO THIS PERMIT ARE IN THE CURRENT BLUE BEAM SESSION ID 409-927-927, THE MASTER SET OF CONSTRUCTION PLANS ARE LOCATED IN BLUE BEAM SESSION ID 917-811-769. TC-COM-0323-00820/BLDG 19/CLUBHOUSE, TC-COM-0423-00974/BLDG 18/MAINT BLDG, TC-COM-0423-00975/POOL RAMADA, TC-COM-0423-00976/PLAYGROUND RAMADA
05/08/2023 Site Zoning APPROVED SPECS SPECIFIC TO THIS PERMIT ARE IN THE CURRENT BLUE BEAM SESSION ID 409-927-927, THE MASTER SET OF CONSTRUCTION PLANS ARE LOCATED IN BLUE BEAM SESSION ID 917-811-769. TC-COM-0323-00820/BLDG 19/CLUBHOUSE, TC-COM-0423-00974/BLDG 18/MAINT BLDG, TC-COM-0423-00975/POOL RAMADA, TC-COM-0423-00976/PLAYGROUND RAMADA
05/12/2023 Bldg Permits - Post Review PENDING ASSIGNMENT SPECS SPECIFIC TO THIS PERMIT ARE IN THE CURRENT BLUE BEAM SESSION ID 409-927-927, THE MASTER SET OF CONSTRUCTION PLANS ARE LOCATED IN BLUE BEAM SESSION ID 917-811-769. TC-COM-0323-00820/BLDG 19/CLUBHOUSE, TC-COM-0423-00974/BLDG 18/MAINT BLDG, TC-COM-0423-00975/POOL RAMADA, TC-COM-0423-00976/PLAYGROUND RAMADA
05/05/2023 External Reviewers - SAFEBuilt REQUIRES RESUBMIT Activity Number: TC-COM-0323-00830/BLDG 19/CLUBHOUSE. TC-COM-0423-00974/BLDG 18/MAINT BLDG, TCCOM-0423-00975/POOL RAMADA, TC-COM-0423-00976/PLAYGROUND RAMADA

GENERAL:
Provide written responses to all review comments.
Provide a complete plan set.
Provide additional documents as requested by review staff.

STRUCTURAL REVIEW COMMENTS:
Conditionally Approved
NOTE: Every effort has been made to identify the code violations. Any oversight by the review team shall not be considered an authority to violate, set aside, cancel or alter applicable codes or ordinances. The plan review and permit issuance shall not be considered a warranty or guarantee. The Structural Engineer is responsible for following ALL applicable Federal, State and local Municipal Codes and Ordinances


BUILDING REVIEW COMMENTS:
Denied
1. Sheet A0.3: The occupant load for business area are calculated incorrectly. Provide an updated occupant load calculation using the correct occupant load factor in accordance with Table 1004.5.


MECHANICAL REVIEW COMMENTS:
Conditionally Approved
Approved/subject to field approval


ELECTRICAL REVIEW COMMENTS
DeniedE002: Confirm that the calculated Total Shielded Lumens are below the acceptable value of Tucson’s requirements.
E003: Details 1 & 3 do not call out conductors. Is this information provided elsewhere?
ES102: Missing Keynote #11 description for an R2 symbol and could not locate Keynote 10.
ES103:
Could not locate Equipment Keynote 5.
Buildings should have 1-2 outdoor service receptacles.
EL101: Need to perform and provide an internal lighting comcheck for all common/shared buildings ie everything on this sheet.
EP601: All panels are incorrectly called out as 240/120V Wye. Wye needs to be removed.
EP702:
Wire and Conduit Keynote #3 is undersized or CB shown by MDP diagram is oversized. Coordinate.
Panel incorrectly called out as 240/120V Wye. Wye needs to be removed.


PLUMBING REVIEW COMMENTS:
Denied
First Plumbing Review:
1). Provide Gas fire place make & model on plan page P4.1 or A3.5 - IFGC 301.3, 305.1
2). Illustrate fire place combustion air & exhaust routing/method on plan page M1.0 -IFGC 304, 503.1


If you require additional clarification regarding these comments, please contact Doris Benoit at doris.benoit@tucsonaz.gov
05/05/2023 Fire New Construction REVIEW COMPLETED
04/18/2023 PDSD Application Completeness REVIEW COMPLETED SPECS SPECIFIC TO THIS PERMIT ARE IN THE CURRENT BLUE BEAM SESSION ID 409-927-927, THE MASTER SET OF CONSTRUCTION PLANS ARE LOCATED IN BLUE BEAM SESSION ID 917-811-769. TC-COM-0323-00820/BLDG 19/CLUBHOUSE, TC-COM-0423-00974/BLDG 18/MAINT BLDG, TC-COM-0423-00975/POOL RAMADA, TC-COM-0423-00976/PLAYGROUND RAMADA