Permit Number: TC-COM-0423-00974
Parcel: 141367940

Review Status: Approved

Review Details: COMMERCIAL REVIEW - FULL v.2

Permit Number - TC-COM-0423-00974
Review Name: COMMERCIAL REVIEW - FULL v.2
Review Status: Approved
Review Date Reviewer's Name Type of Review Description Status Comments
07/05/2023 External Reviewers - SAFEBuilt APPROVED Activity Number: TC-COM-0323-00830/BLDG 19/CLUBHOUSE, TC-COM-0423-00974/BLDG 18/MAINT BLDG, TC-COM-0423-00975/POOL RAMADA, TC-COM-0423-00976/PLAYGROUND RAMADA

GENERAL:
Provide written responses to all review comments.
Provide a complete plan set.
Provide additional documents as requested by review staff.


Structural(S) Reviewer
Daljit Benipal
dbenipal@safebuilt.com
Conditionally Approved
Reason:
Date Completed : 5/4/2023 8:21:04 PM
NOTE: Every effort has been made to identify the code violations. Any oversight by the review team shall not be considered an authority to violate, set aside, cancel or alter applicable codes or ordinances. The plan review and permit issuance shall not be considered a warranty or guarantee. The Structural Engineer is responsible for following ALL applicable Federal, State and local Municipal Codes and Ordinances.


Building(B) Reviewer
Andrew Bevis
abevis@safebuilt.com
Approved
Reason:
Date Completed : 7/3/2023 1:41:44 PM


Mechanical(M) Reviewer
Neil Samaan
nsamaan@safebuilt.com
Conditionally Approved
Reason:
Date Completed : 4/23/2023 11:48:08 AM
Approved/subject to field approval


Electrical(E) Reviewer
Ron Ross
rross@safebuilt.com
Approved
Reason:
Date Completed : 6/28/2023 5:08:54 PM
Electrical Review of Encantada
By: Ron Ross PE
ES103: Buildings should have 1-2 outdoor service receptacles. However, this is not a code requirement, just a suggestion to provide service receptacles at the ground floor


Plumbing(P) Reviewer
Perry Hendershott
phendershott@safebuilt.com
Conditionally Approved
Reason:
Date Completed : 7/2/2023 10:04:58 PM
Second Plumbing Review:
1). OK - Provide Gas fire place make & model on plan page P4.1 or A3.5 - IFGC 301.3, 305.1 **subject to manufactureres installation requirements & field inspections see plan page M1.0 & response narrative**
2).OK- Illustrate fire place combustion air & exhaust routing/method on plan page M1.0 -IFGC 304, 503.1 **subject to manufactureres installation requirements & field inspections see plan page M1.0 & response narrative**
07/05/2023 Bldg Permits - Post Review REVIEW COMPLETED MASTER SET OF CONSTRUCTION PLANS ARE LOCATED at Studio Session 592-477-962 WITH PERMIT TC-COM-0323-00830/BLDG 19/CLUBHOUSE, TC-COM-0423-00974/BLDG 18/MAINT BLDG, TC-COM-0423-00975/POOL RAMADA, TC-COM-0423-00976/PLAYGROUND RAMADA
06/27/2023 PDSD Application Completeness REVIEW COMPLETED