Microfiche records prior to 2006 have not been completely digitized and may not be available yet on PRO. If you can not find what you are looking for please submit a records request.

Permit Number: TC-COM-0423-00974
Parcel: 141367940

Review Status: Requires Resubmit

Review Details: COMMERCIAL REVIEW - FULL v.1

Permit Number - TC-COM-0423-00974
Review Name: COMMERCIAL REVIEW - FULL v.1
Review Status: Requires Resubmit
Review Date Reviewer's Name Type of Review Description Status Comments
10/30/2023 Site Engineering APPROVED TC-COM-0323-00830 (STUDIO SESSION 560-687-683), TC-COM-0423-00974-TC-COM-0423-00976
10/25/2023 Site Zoning APPROVED TC-COM-0323-00830 (STUDIO SESSION 560-687-683), TC-COM-0423-00974-TC-COM-0423-00976
11/01/2023 Water - PDSD APPROVED TC-COM-0323-00830 (STUDIO SESSION 560-687-683), TC-COM-0423-00974-TC-COM-0423-00976
11/01/2023 Bldg Permits - Post Review PENDING ASSIGNMENT TC-COM-0323-00830 (STUDIO SESSION 560-687-683), TC-COM-0423-00974-TC-COM-0423-00976
10/25/2023 External Reviewers - SAFEBuilt REQUIRES RESUBMIT Structural(S) Reviewer
Madeline Nelson
mnelson@safebuilt.com
Approved
Reason:
Date Completed : 10/23/2023 9:27:57 PM



Building(B) Reviewer
Andrew Bevis
abevis@safebuilt.com
Approved
Reason:
Date Completed : 10/23/2023 1:22:51 PM



Mechanical N/A



Electrical(E) Reviewer
Ron Ross
rross@safebuilt.com
Approved with Comments
Reason:
Date Completed : 10/23/2023 11:32:30 AM
Electrical Review
By: Ron Ross PE
Updated the Dog Wash Station location is missing keynote 13 on sheet ES102

The added electrical layout for ‘RAMADA-1’ is detail #4 not #3 as shown on ES103



Plumbing(P) Reviewer
Perry Hendershott
phendershott@safebuilt.com
Denied
Reason:
Date Completed : 10/24/2023 10:17:49 PM
First Revision Plumbing Review:
1). Total gas load on plan page P1.1 needs to be updated to reflect new total load -IFGC 402


2), Total Gas load on plan P2.2 is incorrect -IFGC 402

3). Provide product spec info for the K9000 truBlu dog washer liste on plan page P4.1 , A High hazard Backflow will be required, Per the product website the hand sprayer can be located below flood rim & unit has shampoo & flee bath injection options - IPC 608

4). Provide letter from utility authority that allows the pet fountain drain to potentially collect storm water or provide protection on plan page P1.4 -IPC 1101.3

5). Dog washer on P1.2 & P4.1 needs hot water -IPC 607.1
10/24/2023 Fire New Construction REVIEW COMPLETED
10/09/2023 PDSD Application Completeness REVIEW COMPLETED