Permit Number: TC-COM-0423-00974
Parcel: 141367940

Review Status: Approved

Review Details: COMMERCIAL REVIEW - FULL v.3

Permit Number - TC-COM-0423-00974
Review Name: COMMERCIAL REVIEW - FULL v.3
Review Status: Approved
Review Date Reviewer's Name Type of Review Description Status Comments
01/30/2024 Bldg Permits - Post Review Express REVIEW COMPLETED
01/30/2024 External Reviewers - SAFEBuilt REVIEW COMPLETED Structural(S) Reviewer
Madeline Nelson
mnelson@safebuilt.com
Approved
Reason:
Date Completed : 10/23/2023 9:27:57 PM



Building(B) Reviewer
Andrew Bevis
abevis@safebuilt.com
Approved
Reason:
Date Completed : 10/23/2023 1:22:51 PM



Mechanical N/A



Electrical(E) Reviewer
Ron Ross
rross@safebuilt.com
Approved with Comments
Reason:
Date Completed : 10/23/2023 11:32:30 AM
Electrical Review
By: Ron Ross PE
Updated the Dog Wash Station location is missing keynote 13 on sheet ES102
The added electrical layout for ‘RAMADA-1’ is detail #4 not #3 as shown on ES103



Plumbing(P) Reviewer
Perry Hendershott
phendershott@safebuilt.com
Approved
Reason:
Date Completed : 1/28/2024 2:43:35 PM
Third Revision Plumbing Review:OK
1).Resolved- Total gas load on plan page P1.1 needs to be updated to reflect new total load -IFGC 402 ** Total Load should be 2085 CFH**

2), Resolved-Total Gas load on plan P2.2 is incorrect -IFGC 402 ** Total Load should be 2085 CFH**

3). Resolved-Provide product spec info for the K9000 truBlu dog washer liste on plan page P4.1 , A High hazard Backflow will be required, Per the product website the hand sprayer can be located below flood rim & unit has shampoo & flee bath
injection options - IPC 608 ** Backflow info not provided**

4). Resolved-Provide letter from utility authority that allows the pet fountain drain to potentially collect storm water or provide protection on plan page P1.4 -IPC 1101.3

5). Resolved-Dog washer on P1.2 & P4.1 needs hot water -IPC 607.1
01/19/2024 PDSD Application Completeness Express REVIEW COMPLETED