Permit Review Detail
Review Status: Requires Resubmit
Review Details: COMMERCIAL REVIEW - FULL v.2
Permit Number - TC-COM-0423-00964
Review Name: COMMERCIAL REVIEW - FULL v.2
Review Status: Requires Resubmit
| Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
|---|---|---|---|---|---|
| 12/19/2023 | Commercial Structural | APPROVED | |||
| 12/19/2023 | Bldg Permits - Post Review Express | PENDING ASSIGNMENT | |||
| 12/19/2023 | Commercial Electrical | REQUIRES RESUBMIT | Please address the electrical plan review comments and provide a written response. 1. Previous electrical review comment #1 is not completely addressed.. Provide full compliance with the 2012 City of Tucson Outdoor Lighting Code for the new Canopy lighting. 1a. To be exempt from providing lumen calculations for the parcel, the new under canopy lighting must have Full Cut-Off shielding, and lamp output color temperature not to exceed 3500K, OLC section 401.2.1(3) and 402.1. Please verify and include the information in the Lighting Plan. Otherwise submit complete lighting plans that meet the requirements of OLC section 104 ‘Plan Submittal Requirements’. Ref; 2018 IBC section 107.2.1, 2017 NEC, 2012 City of Tucson Outdoor Lighting Code (OLC). |
||
| 11/24/2023 | PDSD Application Completeness Express | REVIEW COMPLETED |