Permit Number: TC-COM-0423-00959
Parcel: 119181070

Address:
728 W AJO WY

Review Status: Requires Resubmit

Review Details: BUILDING DEFERRED SUBMITTAL REVIEW v.2

Permit Number - TC-COM-0423-00959
Review Name: BUILDING DEFERRED SUBMITTAL REVIEW v.2
Review Status: Requires Resubmit
Review Date Reviewer's Name Type of Review Description Status Comments
05/07/2026 Bldg Permits - Post Review Express PENDING ASSIGNMENT
05/07/2026 Piling/Caisson Inspection (Deferred Submittal) Express REQUIRES RESUBMIT The field report provided indicated that the concrete did not meet the req'd specifications. Please provide the report showing retesting or concrete meeting the project spec.
05/07/2026 Special Inspection Certificate Review (Deferred Submittal) Express REQUIRES RESUBMIT Please include the registered special inspector's name that performed the inspections on the SIC. Outdoor lighting is required to be on it's own certificate and must also be performed by a registered inspector.
https://www.tucsonaz.gov/files/sharedassets/public/v/1/pdsd/documents/engineering-code/inspections/odl_special_inspection_certificate.pdf
05/07/2026 Other Inspection Reports (Deferred Submittal) Express REVIEW COMPLETED High Strength Bolts
05/07/2026 PDSD Application Completeness Express REVIEW COMPLETED