Permit Review Detail
Review Status: Requires Resubmit
Review Details: COMMERCIAL REVIEW - FULL v.2
Permit Number - TC-COM-0423-00958
Review Name: COMMERCIAL REVIEW - FULL v.2
Review Status: Requires Resubmit
| Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
|---|---|---|---|---|---|
| 09/12/2024 | Commercial Electrical | APPROVED | |||
| 10/16/2024 | Bldg Permits - Post Review Express | PENDING ASSIGNMENT | |||
| 09/30/2024 | Commercial Structural | REQUIRES RESUBMIT | ACTIVITY NO. TC-COM-1222-00238 ADDRESS/PARCEL: (211 S 4TH AV TUCSON, AZ 85701) Submit your revised drawings along with a detailed response letter, which states how all Building Review Section comments were addressed. The submitted documents were incomplete and a thorough plan review could not be performed. Please be aware, new comments may arise with the next review. Review will not proceed without the response letter. COMMENTS: 1. The depth of the steel structure on Sheet S2.3 is 33’-1 7/8”. The depth of the steel structure on Sheet 7 Enlarged Site Plan 2 is 26’-7 ¼”. That is a difference of close to 7 ft. The required setback will not be compliant. Please resolve this with Site Zoning and Site Engineering. 2. Please resubmit. |
||
| 10/02/2024 | Site Engineering | REQUIRES RESUBMIT | see commercial structural comment | ||
| 10/16/2024 | Site Zoning | REQUIRES RESUBMIT | See Commercial Structure comment. The structure will not meet setback requirement, the structure is bigger than shown on the site plan. | ||
| 08/30/2024 | PDSD Application Completeness Express | REVIEW COMPLETED |