Permit Number: TC-COM-0326-00336
Parcel: 14029037B

Review Status: Requires Resubmit

Review Details: COMMERCIAL REVIEW - LIMITED v.2

Permit Number - TC-COM-0326-00336
Review Name: COMMERCIAL REVIEW - LIMITED v.2
Review Status: Requires Resubmit
Review Date Reviewer's Name Type of Review Description Status Comments
03/24/2026 Bldg Permits - Post Review Express PENDING ASSIGNMENT
03/24/2026 Commercial Electrical REQUIRES RESUBMIT Commercial Electrical Review TC-COM-0326-00336 (3160 E TRANSCON WY TUCSON, AZ 85706)
Plan review for the above referenced structure has been completed. This letter reflects comments to be addressed. Provide updated Plans/calculations and a written response Letter to each of the notated items indicating action taken. Resubmitted plans that do not contain a written response Letter addressing each of the notated items indicating action taken, may be delayed until response letter is received.
Code reference, 2024 International Building Code (IBC), 2023 National Electrical Code (NEC).

Contact Jeremy Hamblin with any questions: Jeremy.hamblin@tucsonaz.gov

1. The currently adopted codes are the 2023 National Electrical Code, and the 2024 ICC. List the correct code for compliance on the plans.
2. Provide Panel Schedules for each of the new panels. Show the bus rating and AIC ratings of each.
3. Provide Fault Current Analysis and show new equipment AIC rating sufficient to withstand the calculated Fault Current. Provide Available Fault Current calculations from TEP transformers to all new equipment, 2023 NEC 110.24.
4. Show new Panel’s and other new equipment with AIC ratings greater than or equal to the Available Fault Currents calculated, 2023 NEC 110.10.
5. The provided plans indicate that there is only one branch circuit being added to Sub Panel A2. Please note on the plans that no other loads shall be added to A1-A3 without permits.