Permit Number: TC-COM-0325-00628
Parcel: 122170710

Review Status: Requires Resubmit

Review Details: COMMERCIAL REVIEW - FULL REVISION v.2

Permit Number - TC-COM-0325-00628
Review Name: COMMERCIAL REVIEW - FULL REVISION v.2
Review Status: Requires Resubmit
Review Date Reviewer's Name Type of Review Description Status Comments
03/09/2026 Commercial Building Standard NOT REQUIRED
03/06/2026 Fire New Construction Standard NOT REQUIRED
02/23/2026 Outdoor Lighting Standard NOT REQUIRED no changes to the outdoor lighting on this revision.
02/13/2026 Site Engineering Standard NOT REQUIRED
03/09/2026 Site Zoning Standard NOT REQUIRED
03/09/2026 Bldg Permits - Post Review Express PENDING ASSIGNMENT
02/24/2026 Commercial Electrical Standard REQUIRES RESUBMIT Commercial Electrical Review TC-COM-0325-00628 (3429 E WILLARD ST TUCSON, AZ 85716)
Plan review for the above referenced structure has been completed. This letter reflects comments to be addressed. Provide updated Plans/calculations and a written response Letter to each of the notated items indicating action taken. Resubmitted plans that do not contain a written response Letter addressing each of the notated items indicating action taken, may be delayed until response letter is received.
Code reference, 2018 International Building Code (IBC), 2017 National Electrical Code (NEC).

Contact Jeremy Hamblin with any questions: Jeremy.hamblin@tucsonaz.gov


1. Please submit updated electrical sheets that are clear and legible. The rescanned sheets are not clear.
2. If the intent is to install the solar system as part of this permit, then please submit complete solar design, including complete one and three line diagrams, all warning labels and locations, and specification sheets for all components.
3. Subpanel H requires a Main Breaker to protect the bus bar. NEC 705.12(B)(2)(1)(b).
02/12/2026 PDSD Application Completeness Express REVIEW COMPLETED
03/05/2026 Water - PDSD Standard REVIEW COMPLETED no changes on this revision.