Permit Review Detail
Review Status: Requires Resubmit
Review Details: COMMERCIAL REVIEW - FULL v.1
Permit Number - TC-COM-0325-00552
Review Name: COMMERCIAL REVIEW - FULL v.1
Review Status: Requires Resubmit
| Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
|---|---|---|---|---|---|
| 04/16/2025 | Commercial Mechanical Standard | APPROVED | |||
| 04/17/2025 | Commercial Plumbing Standard | APPROVED | |||
| 04/16/2025 | Water - PDSD Standard | APPROVED | |||
| 04/21/2025 | Bldg Permits - Post Review Express | PENDING ASSIGNMENT | |||
| 04/21/2025 | Commercial Building Standard | REQUIRES RESUBMIT | ACTIVITY NO. TC-COM-0325-00552 ADDRESS/PARCEL: (1365 W GRANT RD TUCSON, AZ 85745) Submit your revised drawings along with a detailed response letter, which states how all Building Review Section comments were addressed. Please paste the review comment individually and enter your response directly below it. Please do this for every comment. Review will not proceed without the response letter. The submitted documents were incomplete and a thorough plan review could not be performed. Please be aware, new comments may arise with the next review. Should the above not followed, it may delay your approval. COMMENTS: 1. Sheet C1 – Applicable Codes a. Please add Arizona Administrative Code Title 18 Chapter 5 for Public and Semi-Public Swimming Pools 2. Sheet A1.0 – Accessible Suites a. Identify the required accessible suites on Hotel Floor Pla – Bottom Level complying to ICC A117.1. b. Ensure to provide the required number of suites complying to ICC A117.1. c. Ensure to comply to Grab bars ICC ANSI A117.1 section 604.5, toilet and bathing facilities, grab bars and shower seat reinforcement sec 1104.11 ICC A117.1 3. Sheet A1.5 – Pool Barrier, sign, equipment, etc. a. Keynote refer to new pool fence detail drawing. This was not provided, please add this to your drawings. b. 5 ft high barrier is required. Please refer to Arizona Administrative Code Title 18 Chapter 5 for Public and Semi-Public Swimming Pools c. Pool Area – Enlarged Plan i. During Construction, signs and required equipment tend to disappear or mislocated. ii. On the Pool Area - Enlarged Plan, locate and label the location of flotation devices, shepherd crook, signs, rules and regulations, etc complying to Arizona Administrative Code Title 18 Chapter 5 for Public and Semi-Public Swimming Pools R18-5-238 and R18-5-222 warning signs. 4. Additionally please list the required special inspections on the plans, preferably on Sheet C1. Additionally, provide the City of Tucson Special Inspection Certificate(s) with Parts A and B completed with the next submittal. IBC 107.1 SI form link: https://www.tucsonaz.gov/files/sharedassets/public/v/1/city-services/planning-development-services/documents/special_inspection_certificate.pdf 5. Please resubmit. Should you have any questions about these comments, I can be reached at Justin.Eder@tucsonaz.gov or 520-837-4976Should you have any questions about these comments, I can be reached at Justin.Eder@tucsonaz.gov or 520-837-4976 |
||
| 04/02/2025 | Commercial Electrical Standard | REQUIRES RESUBMIT | Commercial Electrical Review TC-COM-0325-00552 (1365 W GRANT RD TUCSON, AZ 85745) Plan review for the above referenced structure has been completed. This letter reflects comments to be addressed. Provide updated Plans/calculations and a written response Letter to each of the notated items indicating action taken. Resubmitted plans that do not contain a written response Letter addressing each of the notated items indicating action taken, may be delayed until response letter is received. Code reference, 2018 International Building Code (IBC), 2017 National Electrical Code (NEC). 1. Provide an electrical demolition plan showing all demolished circuits, appliances, fixtures, etc. 2. Provide a complete electrical plan-set showing all proposed electrical work. 3. Should include but not be limited to: a. Provide a panel schedule showing the circuits that are being modified and added. b. Designate the circuit number, that corresponds to the panel schedule, at the location of each new or modified light fixture, receptacle, appliance, and equipment disconnect switch, NEC arts;300 and 408.4. c. Show all wiring methods in detail for all branch circuit wiring along with branch circuit and breaker panel designations and correlate with the panel schedules. NEC arts;300 and 408.4. Contact Jeremy Hamblin with any questions: Jeremy.hamblin@tucsonaz.gov |
||
| 04/02/2025 | Outdoor Lighting Standard | REQUIRES RESUBMIT | Outdoor Lighting Review TC-COM-0325-00552 (1365 W GRANT RD TUCSON, AZ 85745) https://www.tucsonaz.gov/files/sharedassets/public/v/1/pdsd/documents/building-code/2012_outdoor_lighting_code_.pdf 1. Clarify if any outdoor lighting is being added or modified and provide the following if changes are being made: a. Provide an outdoor lighting plan that meets the requirements of OLC 104.2. Show/locate the different light sources on your site plan. Number/label the light fixtures on your table and use the same number on your site plan for both internal and external lights. b. Show compliance with City of Tucson Outdoor Lighting Code with an approved lighting calculation in accordance with OLC 3.1.2. Include all exterior fixtures on the property in the calculations. Show unshielded fixtures with a maximum of 3,000 lumens, OLC 401.4. Show lamps with a maximum of 3500K color temperature, OLC 402.1. c. Show compliance to total outdoor light output per 2012 City of Tucson/Pima County Outdoor Lighting Code section 401.2. Total outdoor light output shall not exceed the lumen limits listed in Table 401.1. 4. E1.1 – Lighting Code section 104.2.2. d. Submit catalogue or specification sheets of all proposed new outdoor lighting fixtures illustrating the type of fixture, color temperature, lumens rating and whether full cut-off or unshielded. Contact Jeremy Hamblin with any questions: Jeremy.hamblin@tucsonaz.gov |
||
| 04/17/2025 | Site Engineering Standard | REQUIRES RESUBMIT | TC-COM-0325-00552 1365 W GRANT RD Site engineering comments are as follows: 1. Although the site plans match, TC-COM-0325-00552 cannot be approved until TD-DEV-0325-00073 is approved by all reviewers. UDC Article 3.3.3.7.a Ryan Insalaco – ryan.insalaco@tucsonaz.gov |
||
| 04/15/2025 | Site Zoning Standard | REQUIRES RESUBMIT | FROM: PDSD Zoning Review Section PROJECT: TC-COM-0325-00552 - TD-DEV-0325-00073 1365 W GRANT RD - I-1 Travelers Accommodation, Lodging (1st Review) TRANSMITTAL DATE: April 15, 2025 COMMENTS: Resubmit revised drawings along with a detailed response letter, which states how all Zoning Review Section comments were addressed. This site is located in the I-1 zone (UDC 4.7.29). Travelers Accommodation, Lodging – W/ Alcoholic Beverage Service as an accessory use is an approved use in the zone (UDC Table 4.8-4), subject to Use Specific Standards 4.9.13.Q, 4.9.4.V.1 & .2, & 4.9.4.C.3. 1. Unit Development Package (DP) TD-DEV-0325-00073 is approved by all review agencies Zoning cannot approve this plan. If you have any questions about this transmittal, please contact Zone1.desk@tucsonaz.gov. |
||
| 04/09/2025 | Fire New Construction Standard | REVIEW COMPLETED | Fire Sprinklers or fire alarm alterations requires a separate permit. | ||
| 03/24/2025 | PDSD Application Completeness Express | REVIEW COMPLETED |