Permit Number: TC-COM-0325-00552
Parcel: 11516019U

Address:
1365 W GRANT RD

Review Status: In Review

Review Details: COMMERCIAL REVIEW - FULL v.2

Permit Number - TC-COM-0325-00552
Review Name: COMMERCIAL REVIEW - FULL v.2
Review Status: In Review
Review Date Reviewer's Name Type of Review Description Status Comments
05/27/2026 Commercial Building Standard APPROVED
05/19/2026 Outdoor Lighting Standard NOT REQUIRED No modifications to the outdoor lighting.
N/A Bldg Permits - Post Review Express PENDING ASSIGNMENT
N/A Commercial Mechanical Standard PENDING ASSIGNMENT
N/A Site Engineering Standard PENDING ASSIGNMENT
N/A Site Zoning Standard PENDING ASSIGNMENT
05/19/2026 Commercial Electrical Standard REQUIRES RESUBMIT Commercial Electrical Review TC-COM-0325-00552 (1365 W GRANT RD TUCSON, AZ 85745)
Plan review for the above referenced structure has been completed. This letter reflects comments to be addressed. Provide updated Plans/calculations and a written response Letter to each of the notated items indicating action taken. Resubmitted plans that do not contain a written response Letter addressing each of the notated items indicating action taken, may be delayed until response letter is received.
Code reference, 2018 International Building Code (IBC), 2017 National Electrical Code (NEC).

>>> Previous comments were not addressed.

1. Provide an electrical demolition plan showing all demolished circuits, appliances, fixtures, etc.
2. Provide a complete electrical plan-set showing all proposed electrical work.
3. Should include but not be limited to:
a. Provide a panel schedule showing the circuits that are being modified and added.
b. Designate the circuit number, that corresponds to the panel schedule, at the location of each new or modified light fixture, receptacle, appliance, and equipment disconnect switch, NEC arts;300 and 408.4.
c. Show all wiring methods in detail for all branch circuit wiring along with branch circuit and breaker panel designations and correlate with the panel schedules. NEC arts;300 and 408.4.

Contact Jeremy Hamblin with any questions: Jeremy.hamblin@tucsonaz.gov
05/13/2026 PDSD Application Completeness Express REVIEW COMPLETED