Permit Number: TC-COM-0325-00542
Parcel: 14042025A

Review Status: Requires Resubmit

Review Details: COMMERCIAL REVIEW - FULL v.1

Permit Number - TC-COM-0325-00542
Review Name: COMMERCIAL REVIEW - FULL v.1
Review Status: Requires Resubmit
Review Date Reviewer's Name Type of Review Description Status Comments
04/04/2025 Commercial Plumbing Standard APPROVED Reviewer - See Internal Notes

Plumbing(P) Reviewer
Janet Matz
jmatz@safebuilt.com
Approved
Reason:
Date Completed : 4/4/2025 2:51:34 AM
2717 E Corona Road IT office improvements
TC-COM-0325-00539 Unit 110
TC-COM-0325-00544 Unit 190
TC-COM-0325-00543 Unit 170
TC-COM-0325-00542 Unit 160
TC-COM-0325-00541 Unit 150
TC-COM-0325-00540 Unit 140
04/07/2025 Site Zoning Standard APPROVED Reviewer - See Internal Notes
04/15/2025 Bldg Permits - Post Review Express PENDING ASSIGNMENT
04/04/2025 Commercial Building Standard REQUIRES RESUBMIT Reviewer - See Internal Notes

Structural(S) Reviewer
Janet Matz
jmatz@safebuilt.com
Denied
Reason:
Date Completed : 4/4/2025 2:56:21 AM
2717 E Corona Road IT office improvements
TC-COM-0325-00539 Unit 110
TC-COM-0325-00544 Unit 190
TC-COM-0325-00543 Unit 170
TC-COM-0325-00542 Unit 160
TC-COM-0325-00541 Unit 150
TC-COM-0325-00540 Unit 140
1. Structural Calculations- Update the codes listed on the calculations to indicate the City of Tucson and remove the
reference to the State of Nevada.


Building(B) Reviewer
Janet Matz
jmatz@safebuilt.com
Denied
Reason:
Date Completed : 4/4/2025 2:53:14 AM
2717 E Corona Road IT office improvements
TC-COM-0325-00539 Unit 110
TC-COM-0325-00544 Unit 190
TC-COM-0325-00543 Unit 170
TC-COM-0325-00542 Unit 160
TC-COM-0325-00541 Unit 150
TC-COM-0325-00540 Unit 140
All corrections must be clouded, delta numbered, with a brief explanation within the plan sheet or the title block. Please
include with the resubmittal a separate response narrative, which is numbered or itemized to correspond to each of the noted
plan review comments items.
1. General Comment- COMcheck Envelope- Compliance Certificate for Unit 140 was missing from the submittal.
2. Sheet G0.0 Cover Sheet- Note on the drawings that additional safety systems may be required depending on the final
tenant specific use occupancy classification.
3. Sheet G0.0 Cover Sheet- Correct the Sheet Index so it matches the drawings that were provided. Sheets P4.7 and
P4.8 are missing on the list as well as sheets E2.4 and E2.5. Sheets M5.1 and M5.2 are listed twice.
4. Sheet G0.0 Cover Sheet- Indicate the Alteration Level of the work in the General Building Code Summary that is in
accordance with 2018 IEBC Section 600.
5. Sheet A1.1 Overall Suite 110- Correct the total occupancy on the Occupancy Load Schedule. The total occupancy
when rounded up should be 91. 2018 IBC 1004.5.
6. Sheet A1.3 Overall Suite 140- Correct the total occupancy on the Occupancy Load Schedule. The total occupancy
when rounded up should be 76. 2018 IBC 1004.5.
7. Sheet A1.5 Overall Suite 150- Correct the total occupancy on the Occupancy Load Schedule. The total occupancy
when rounded up should be 15 + 46 for a total of 61. 2018 IBC 1004.5.
8. Sheet A1.7 Overall Suite 160- Correct the total occupancy on the Occupancy Load Schedule. The total occupancy
when rounded up should be 8 + 23 for a total of 31. 2018 IBC 1004.5.
9. Sheet A1.9 Overall Suite 170- Correct the total occupancy on the Occupancy Load Schedule. The total occupancy
when rounded up should be 8 + 23 for a total of 31. 2018 IBC 1004.5.
10. Sheet A1.11 Overall Suite 190- Correct the total occupancy on the Occupancy Load Schedule. The total occupancy
when rounded up should be 15 + 45 for a total of 60. 2018 IBC 1004.5.
04/04/2025 Commercial Electrical Standard REQUIRES RESUBMIT Reviewer - See Internal Notes
Electrical(E) Reviewer
Janet Matz
jmatz@safebuilt.com
Denied
Reason:
Date Completed : 4/4/2025 2:54:21 AM
2717 E Corona Road IT office improvements
TC-COM-0325-00539 Unit 110
TC-COM-0325-00544 Unit 190
TC-COM-0325-00543 Unit 170
TC-COM-0325-00542 Unit 160
TC-COM-0325-00541 Unit 150
TC-COM-0325-00540 Unit 140
1. General Comment- Provide an Interior Lighting COMcheck Compliance Certificate or other approved methodology for
the project for the new proposed lighting. 2018 IECC.
04/04/2025 Commercial Mechanical Standard REQUIRES RESUBMIT Reviewer - See Internal Notes

Mechanical(M) Reviewer
Janet Matz
jmatz@safebuilt.com
Denied
Reason:
Date Completed : 4/4/2025 2:55:24 AM
2717 E Corona Road IT office improvements
TC-COM-0325-00539 Unit 110
TC-COM-0325-00544 Unit 190
TC-COM-0325-00543 Unit 170
TC-COM-0325-00542 Unit 160
TC-COM-0325-00541 Unit 150
TC-COM-0325-00540 Unit 140
All corrections must be clouded, delta numbered, with a brief explanation within the plan sheet or the title block. Please
include with the resubmittal a separate response narrative, which is numbered or itemized to correspond to each of the noted
plan review comments items.
1. Sheet M2.0 Mechanical Overall Plan- Note the location of the permanently installed roof ladder or hatch on the plan,
the existing roof is greater than 16 feet above grade. 2018 IMC 306.5.
04/15/2025 Water - PDSD Standard REQUIRES RESUBMIT Reviewer - See Internal Notes
Provide the size of the water meter serving this suite, the size of the backflow preventer associated with the water meter, and the total water demand served by the water meter. Reference: Section 107.2.1, IBC 2018.
04/02/2025 Fire New Construction Standard REVIEW COMPLETED SUITE160:
Fire alarm or fire sprinklers systems alteration requires a separate permit.
03/20/2025 PDSD Application Completeness Express REVIEW COMPLETED
04/14/2025 Site Engineering Standard REVIEW COMPLETED Reviewer - See Internal Notes