Review Details: COMMERCIAL REVIEW - FULL v.2

Permit Number - TC-COM-0325-00519
Review Name: COMMERCIAL REVIEW - FULL v.2
Review Status: Requires Resubmit
Review Date Reviewer's Name Type of Review Description Status Comments
05/19/2025 Bldg Permits - Post Review Express PENDING ASSIGNMENT
04/29/2025 Commercial Building Standard REQUIRES RESUBMIT April 28, 2025
2nd Review

JH6226 LLC
Attn: Josh Herndon
4500 E. Speedway, #64
Tucson, Arizona 85712

Re: BURGER KING
REMODEL AND ADDITION

City of Tucson Permit Number: TC-COM-0325-00519
Stantec Project Number: 185215066
Stantec File Number: TUC-25-038

Plan review for the above referenced project has been completed. This letter reflects comments to be addressed. PLEASE send all response to comments back to the City through the permit portal! Responses sent directly to Stantec will be ignored. Also, please submit complete copies of all permit documents (i.e. plans, calculations, reports, etc.) even if they have not been changed. Please cloud and delta all changes and provide a letter with a written response to each of the comments indicating the action taken.

The scope of this review covers the architectural, structural, plumbing, mechanical, and electrical designs as they relate to the codes adopted by the jurisdiction. All features were checked only to the extent allowed by the submittals provided. All portions of this project are assumed to meet or will meet other departmental requirements, conditions, and concerns before permit approval.

Occupancy
Group Construction
Type Area
(Square feet) Occupant
Load Automatic
Fire Sprinklers Fire
Alarms
A-2 V-B 3,185 82 No No
Separate Permits: Signage.
Deferred Submittals: Prefabricated awnings.
Special Inspections: Epoxy and expansion anchors and outdoor lighting.

ARCHITECTURAL COMMENTS

General

1. Addressed.

2. Addressed.

3. Previous Comment: Note on the cover of the drawings that special inspection is required for epoxy and expansion anchors and outdoor lighting. Also, provide City of Tucson special inspection certificate(s) with Parts A and B completed. Make sure that the owner or their legal representative signs the form. Still Required: A special inspection certificate was not provided for the required outdoor lighting special inspection.

STRUCTURAL COMMENTS

There are no comments.

MECHANICAL COMMENTS

There are no comments.

PLUMBING COMMENTS

Sheet P.1

1. Addressed,

2. Addressed.

Sheet P.2

1. Previous Comment: The plumbing plan indicates a keynote 2 in the dining room at one of the booths. This does not appear to be intentional. Please remove. Still Required: This comment was not addressed.

2. Addressed.

ELECTRICAL COMMENTS

Sheet E.1

1. Addressed.

2. Addressed.

Sheet E.2

1. Addressed.


Should you have any questions regarding the plan review comments, please contact the plan reviewer listed for the appropriate discipline.

Plans reviewed by:
Trevor Bies,
Senior Plan Reviewer
602-338-9922
trevor.bies@stantec.com
04/29/2025 Commercial Electrical Standard REQUIRES RESUBMIT April 28, 2025
2nd Review

JH6226 LLC
Attn: Josh Herndon
4500 E. Speedway, #64
Tucson, Arizona 85712

Re: BURGER KING
REMODEL AND ADDITION

City of Tucson Permit Number: TC-COM-0325-00519
Stantec Project Number: 185215066
Stantec File Number: TUC-25-038

Plan review for the above referenced project has been completed. This letter reflects comments to be addressed. PLEASE send all response to comments back to the City through the permit portal! Responses sent directly to Stantec will be ignored. Also, please submit complete copies of all permit documents (i.e. plans, calculations, reports, etc.) even if they have not been changed. Please cloud and delta all changes and provide a letter with a written response to each of the comments indicating the action taken.

The scope of this review covers the architectural, structural, plumbing, mechanical, and electrical designs as they relate to the codes adopted by the jurisdiction. All features were checked only to the extent allowed by the submittals provided. All portions of this project are assumed to meet or will meet other departmental requirements, conditions, and concerns before permit approval.

Occupancy
Group Construction
Type Area
(Square feet) Occupant
Load Automatic
Fire Sprinklers Fire
Alarms
A-2 V-B 3,185 82 No No
Separate Permits: Signage.
Deferred Submittals: Prefabricated awnings.
Special Inspections: Epoxy and expansion anchors and outdoor lighting.

ARCHITECTURAL COMMENTS

General

1. Addressed.

2. Addressed.

3. Previous Comment: Note on the cover of the drawings that special inspection is required for epoxy and expansion anchors and outdoor lighting. Also, provide City of Tucson special inspection certificate(s) with Parts A and B completed. Make sure that the owner or their legal representative signs the form. Still Required: A special inspection certificate was not provided for the required outdoor lighting special inspection.

STRUCTURAL COMMENTS

There are no comments.

MECHANICAL COMMENTS

There are no comments.

PLUMBING COMMENTS

Sheet P.1

1. Addressed,

2. Addressed.

Sheet P.2

1. Previous Comment: The plumbing plan indicates a keynote 2 in the dining room at one of the booths. This does not appear to be intentional. Please remove. Still Required: This comment was not addressed.

2. Addressed.

ELECTRICAL COMMENTS

Sheet E.1

1. Addressed.

2. Addressed.

Sheet E.2

1. Addressed.


Should you have any questions regarding the plan review comments, please contact the plan reviewer listed for the appropriate discipline.

Plans reviewed by:
Trevor Bies,
Senior Plan Reviewer
602-338-9922
trevor.bies@stantec.com
04/29/2025 Commercial Mechanical Standard REQUIRES RESUBMIT April 28, 2025
2nd Review

JH6226 LLC
Attn: Josh Herndon
4500 E. Speedway, #64
Tucson, Arizona 85712

Re: BURGER KING
REMODEL AND ADDITION

City of Tucson Permit Number: TC-COM-0325-00519
Stantec Project Number: 185215066
Stantec File Number: TUC-25-038

Plan review for the above referenced project has been completed. This letter reflects comments to be addressed. PLEASE send all response to comments back to the City through the permit portal! Responses sent directly to Stantec will be ignored. Also, please submit complete copies of all permit documents (i.e. plans, calculations, reports, etc.) even if they have not been changed. Please cloud and delta all changes and provide a letter with a written response to each of the comments indicating the action taken.

The scope of this review covers the architectural, structural, plumbing, mechanical, and electrical designs as they relate to the codes adopted by the jurisdiction. All features were checked only to the extent allowed by the submittals provided. All portions of this project are assumed to meet or will meet other departmental requirements, conditions, and concerns before permit approval.

Occupancy
Group Construction
Type Area
(Square feet) Occupant
Load Automatic
Fire Sprinklers Fire
Alarms
A-2 V-B 3,185 82 No No
Separate Permits: Signage.
Deferred Submittals: Prefabricated awnings.
Special Inspections: Epoxy and expansion anchors and outdoor lighting.

ARCHITECTURAL COMMENTS

General

1. Addressed.

2. Addressed.

3. Previous Comment: Note on the cover of the drawings that special inspection is required for epoxy and expansion anchors and outdoor lighting. Also, provide City of Tucson special inspection certificate(s) with Parts A and B completed. Make sure that the owner or their legal representative signs the form. Still Required: A special inspection certificate was not provided for the required outdoor lighting special inspection.

STRUCTURAL COMMENTS

There are no comments.

MECHANICAL COMMENTS

There are no comments.

PLUMBING COMMENTS

Sheet P.1

1. Addressed,

2. Addressed.

Sheet P.2

1. Previous Comment: The plumbing plan indicates a keynote 2 in the dining room at one of the booths. This does not appear to be intentional. Please remove. Still Required: This comment was not addressed.

2. Addressed.

ELECTRICAL COMMENTS

Sheet E.1

1. Addressed.

2. Addressed.

Sheet E.2

1. Addressed.


Should you have any questions regarding the plan review comments, please contact the plan reviewer listed for the appropriate discipline.

Plans reviewed by:
Trevor Bies,
Senior Plan Reviewer
602-338-9922
trevor.bies@stantec.com
04/29/2025 Commercial Plumbing Standard REQUIRES RESUBMIT April 28, 2025
2nd Review

JH6226 LLC
Attn: Josh Herndon
4500 E. Speedway, #64
Tucson, Arizona 85712

Re: BURGER KING
REMODEL AND ADDITION

City of Tucson Permit Number: TC-COM-0325-00519
Stantec Project Number: 185215066
Stantec File Number: TUC-25-038

Plan review for the above referenced project has been completed. This letter reflects comments to be addressed. PLEASE send all response to comments back to the City through the permit portal! Responses sent directly to Stantec will be ignored. Also, please submit complete copies of all permit documents (i.e. plans, calculations, reports, etc.) even if they have not been changed. Please cloud and delta all changes and provide a letter with a written response to each of the comments indicating the action taken.

The scope of this review covers the architectural, structural, plumbing, mechanical, and electrical designs as they relate to the codes adopted by the jurisdiction. All features were checked only to the extent allowed by the submittals provided. All portions of this project are assumed to meet or will meet other departmental requirements, conditions, and concerns before permit approval.

Occupancy
Group Construction
Type Area
(Square feet) Occupant
Load Automatic
Fire Sprinklers Fire
Alarms
A-2 V-B 3,185 82 No No
Separate Permits: Signage.
Deferred Submittals: Prefabricated awnings.
Special Inspections: Epoxy and expansion anchors and outdoor lighting.

ARCHITECTURAL COMMENTS

General

1. Addressed.

2. Addressed.

3. Previous Comment: Note on the cover of the drawings that special inspection is required for epoxy and expansion anchors and outdoor lighting. Also, provide City of Tucson special inspection certificate(s) with Parts A and B completed. Make sure that the owner or their legal representative signs the form. Still Required: A special inspection certificate was not provided for the required outdoor lighting special inspection.

STRUCTURAL COMMENTS

There are no comments.

MECHANICAL COMMENTS

There are no comments.

PLUMBING COMMENTS

Sheet P.1

1. Addressed,

2. Addressed.

Sheet P.2

1. Previous Comment: The plumbing plan indicates a keynote 2 in the dining room at one of the booths. This does not appear to be intentional. Please remove. Still Required: This comment was not addressed.

2. Addressed.

ELECTRICAL COMMENTS

Sheet E.1

1. Addressed.

2. Addressed.

Sheet E.2

1. Addressed.


Should you have any questions regarding the plan review comments, please contact the plan reviewer listed for the appropriate discipline.

Plans reviewed by:
Trevor Bies,
Senior Plan Reviewer
602-338-9922
trevor.bies@stantec.com
04/29/2025 Outdoor Lighting Standard REQUIRES RESUBMIT April 28, 2025
2nd Review

JH6226 LLC
Attn: Josh Herndon
4500 E. Speedway, #64
Tucson, Arizona 85712

Re: BURGER KING
REMODEL AND ADDITION

City of Tucson Permit Number: TC-COM-0325-00519
Stantec Project Number: 185215066
Stantec File Number: TUC-25-038

Plan review for the above referenced project has been completed. This letter reflects comments to be addressed. PLEASE send all response to comments back to the City through the permit portal! Responses sent directly to Stantec will be ignored. Also, please submit complete copies of all permit documents (i.e. plans, calculations, reports, etc.) even if they have not been changed. Please cloud and delta all changes and provide a letter with a written response to each of the comments indicating the action taken.

The scope of this review covers the architectural, structural, plumbing, mechanical, and electrical designs as they relate to the codes adopted by the jurisdiction. All features were checked only to the extent allowed by the submittals provided. All portions of this project are assumed to meet or will meet other departmental requirements, conditions, and concerns before permit approval.

Occupancy
Group Construction
Type Area
(Square feet) Occupant
Load Automatic
Fire Sprinklers Fire
Alarms
A-2 V-B 3,185 82 No No
Separate Permits: Signage.
Deferred Submittals: Prefabricated awnings.
Special Inspections: Epoxy and expansion anchors and outdoor lighting.

ARCHITECTURAL COMMENTS

General

1. Addressed.

2. Addressed.

3. Previous Comment: Note on the cover of the drawings that special inspection is required for epoxy and expansion anchors and outdoor lighting. Also, provide City of Tucson special inspection certificate(s) with Parts A and B completed. Make sure that the owner or their legal representative signs the form. Still Required: A special inspection certificate was not provided for the required outdoor lighting special inspection.

STRUCTURAL COMMENTS

There are no comments.

MECHANICAL COMMENTS

There are no comments.

PLUMBING COMMENTS

Sheet P.1

1. Addressed,

2. Addressed.

Sheet P.2

1. Previous Comment: The plumbing plan indicates a keynote 2 in the dining room at one of the booths. This does not appear to be intentional. Please remove. Still Required: This comment was not addressed.

2. Addressed.

ELECTRICAL COMMENTS

Sheet E.1

1. Addressed.

2. Addressed.

Sheet E.2

1. Addressed.


Should you have any questions regarding the plan review comments, please contact the plan reviewer listed for the appropriate discipline.

Plans reviewed by:
Trevor Bies,
Senior Plan Reviewer
602-338-9922
trevor.bies@stantec.com
05/17/2025 Site Engineering Standard REQUIRES RESUBMIT TC-COM-0325-00519
1681 W VALENCIA RD

Site engineering comments are as follows:
1. This commercial building permit cannot be approved until the associated development package, TD-DEV-0325-00080, is approved by all reviewers. UDC Article 3.3.3.7.a
2. As proposed, the building permit plans do not match the development package plans. Keynote 6 on the site plan of the associated development package, “sign base to remain,” is not shown on the building permit.
Ryan Insalaco – ryan.insalaco@tucsonaz.gov
05/19/2025 Site Zoning Standard REQUIRES RESUBMIT ZONING REVIEW TRANSMITTAL

FROM: PDSD Zoning Review

PROJECT:
TC-COM-0325-00519 - TD-DEV-0325-00080
1681 W VALENCIA RD. – C-1
Food Service (2nd Review)

TRANSMITTAL DATE: May 19, 2025

DUE DATE: May 15, 2025

This comment was not addressed. Please resubmit revised drawings and any redlined plans along with a detailed response letter, which states how all Zoning Review Section comments were addressed.

This site is located in the C-1 zone (UDC 4.7.20). food service is a permitted use in the zone (UDC Table 4.8-4), subject to Use Specific Standards 4.9.4.M.1 & 5 and 4.9.13.O.

1. COMMENT: Zoning has reviewed the building plans for compliance with Development Package (DP) TD-DEV-0325-00080, and although the plans appear to match until the DP is approved by all review agencies Zoning cannot approved the building permit.

If you have any questions about this transmittal, please contact Zone1.desk@tucsonaz.gov.
04/24/2025 PDSD Application Completeness Express REVIEW COMPLETED