Permit Review Detail
Review Status: Requires Resubmit
Review Details: COMMERCIAL REVIEW - FULL v.3
Permit Number - TC-COM-0325-00482
Review Name: COMMERCIAL REVIEW - FULL v.3
Review Status: Requires Resubmit
| Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
|---|---|---|---|---|---|
| 08/14/2025 | Bldg Permits - Post Review Express | PENDING ASSIGNMENT | |||
| 07/31/2025 | Commercial Building Standard | REQUIRES RESUBMIT | July 31, 2025 3rd Review ASI Architects Attn: Phillip Veneziano 5931 E. Pima Street Tucson, Arizona 85712 Re: KOCH WAREHOUSE NEW BUILDING City of Tucson Permit Number: TC-COM-0325-00482 Stantec Project Number: 185215066 Stantec File Number: TUC-25-034 Plan review for the above referenced project has been completed. This letter reflects comments to be addressed. PLEASE send all response to comments back to the City through the permit portal! Responses sent directly to Stantec will be ignored. Also, please submit complete copies of all permit documents (i.e. plans, calculations, reports, etc.) even if they have not been changed. Please cloud and delta all changes and provide a letter with a written response to each of the comments indicating the action taken. The scope of this review covers the architectural, structural, plumbing, mechanical, and electrical designs as they relate to the codes adopted by the jurisdiction. All features were checked only to the extent allowed by the submittals provided. All portions of this project are assumed to meet or will meet other departmental requirements, conditions, and concerns before permit approval. Occupancy Group Construction Type Area (Square feet) Occupant Load Automatic Fire Sprinklers Fire Alarms S-1 V-B 5,000 10 No No Separate Permits: None. Deferred Submittals: None. Special Inspections: Earthwork, concrete, and high-strength bolts. ARCHITECTURAL COMMENTS Sheet G1.0 1. Addressed. 2. Previous Comment: A special inspection certificate was not provided for the listed special inspections on the cover sheet for earthwork, concrete, and high-strength bolts. Please provide a special inspection certificate with Parts A and B completed. Still Required: The special inspection certificates provided do not contain special inspection for high-strength bolting. Please provide. 3. Addressed. 4. Addressed. 5. Addressed. 6. Addressed. 7. New Comment: Sheet SP1.0 is missing from the plan set. Please resubmit all sheets included in the plan set. 8. New Comment: The latest submittal is missing documents. Please ensure on the next submittal all required documents are resubmitted. The latest submittal is missing the following: a. Steel building plans b. Steel building calculations c. Foundation calculations Sheet SP1.0 1. Addressed. 2. Addressed. 3. Addressed. Sheet A1.0 1. Addressed. 2. Addressed. 3. Addressed. STRUCTURAL COMMENTS Sheet S1.0 1. Addressed. MECHANICAL COMMENTS There are no comments. PLUMBING COMMENTS Sheet P1.0 1. Addressed. ELECTRICAL COMMENTS General 1. Addressed. 2. Addressed. Sheet E1.0 1. Addressed. 2. Addressed. 3. Addressed. |
||
| 07/31/2025 | Commercial Electrical Standard | REQUIRES RESUBMIT | July 31, 2025 3rd Review ASI Architects Attn: Phillip Veneziano 5931 E. Pima Street Tucson, Arizona 85712 Re: KOCH WAREHOUSE NEW BUILDING City of Tucson Permit Number: TC-COM-0325-00482 Stantec Project Number: 185215066 Stantec File Number: TUC-25-034 Plan review for the above referenced project has been completed. This letter reflects comments to be addressed. PLEASE send all response to comments back to the City through the permit portal! Responses sent directly to Stantec will be ignored. Also, please submit complete copies of all permit documents (i.e. plans, calculations, reports, etc.) even if they have not been changed. Please cloud and delta all changes and provide a letter with a written response to each of the comments indicating the action taken. The scope of this review covers the architectural, structural, plumbing, mechanical, and electrical designs as they relate to the codes adopted by the jurisdiction. All features were checked only to the extent allowed by the submittals provided. All portions of this project are assumed to meet or will meet other departmental requirements, conditions, and concerns before permit approval. Occupancy Group Construction Type Area (Square feet) Occupant Load Automatic Fire Sprinklers Fire Alarms S-1 V-B 5,000 10 No No Separate Permits: None. Deferred Submittals: None. Special Inspections: Earthwork, concrete, and high-strength bolts. ARCHITECTURAL COMMENTS Sheet G1.0 1. Addressed. 2. Previous Comment: A special inspection certificate was not provided for the listed special inspections on the cover sheet for earthwork, concrete, and high-strength bolts. Please provide a special inspection certificate with Parts A and B completed. Still Required: The special inspection certificates provided do not contain special inspection for high-strength bolting. Please provide. 3. Addressed. 4. Addressed. 5. Addressed. 6. Addressed. 7. New Comment: Sheet SP1.0 is missing from the plan set. Please resubmit all sheets included in the plan set. 8. New Comment: The latest submittal is missing documents. Please ensure on the next submittal all required documents are resubmitted. The latest submittal is missing the following: a. Steel building plans b. Steel building calculations c. Foundation calculations Sheet SP1.0 1. Addressed. 2. Addressed. 3. Addressed. Sheet A1.0 1. Addressed. 2. Addressed. 3. Addressed. STRUCTURAL COMMENTS Sheet S1.0 1. Addressed. MECHANICAL COMMENTS There are no comments. PLUMBING COMMENTS Sheet P1.0 1. Addressed. ELECTRICAL COMMENTS General 1. Addressed. 2. Addressed. Sheet E1.0 1. Addressed. 2. Addressed. 3. Addressed. |
||
| 07/31/2025 | Commercial Mechanical Standard | REQUIRES RESUBMIT | July 31, 2025 3rd Review ASI Architects Attn: Phillip Veneziano 5931 E. Pima Street Tucson, Arizona 85712 Re: KOCH WAREHOUSE NEW BUILDING City of Tucson Permit Number: TC-COM-0325-00482 Stantec Project Number: 185215066 Stantec File Number: TUC-25-034 Plan review for the above referenced project has been completed. This letter reflects comments to be addressed. PLEASE send all response to comments back to the City through the permit portal! Responses sent directly to Stantec will be ignored. Also, please submit complete copies of all permit documents (i.e. plans, calculations, reports, etc.) even if they have not been changed. Please cloud and delta all changes and provide a letter with a written response to each of the comments indicating the action taken. The scope of this review covers the architectural, structural, plumbing, mechanical, and electrical designs as they relate to the codes adopted by the jurisdiction. All features were checked only to the extent allowed by the submittals provided. All portions of this project are assumed to meet or will meet other departmental requirements, conditions, and concerns before permit approval. Occupancy Group Construction Type Area (Square feet) Occupant Load Automatic Fire Sprinklers Fire Alarms S-1 V-B 5,000 10 No No Separate Permits: None. Deferred Submittals: None. Special Inspections: Earthwork, concrete, and high-strength bolts. ARCHITECTURAL COMMENTS Sheet G1.0 1. Addressed. 2. Previous Comment: A special inspection certificate was not provided for the listed special inspections on the cover sheet for earthwork, concrete, and high-strength bolts. Please provide a special inspection certificate with Parts A and B completed. Still Required: The special inspection certificates provided do not contain special inspection for high-strength bolting. Please provide. 3. Addressed. 4. Addressed. 5. Addressed. 6. Addressed. 7. New Comment: Sheet SP1.0 is missing from the plan set. Please resubmit all sheets included in the plan set. 8. New Comment: The latest submittal is missing documents. Please ensure on the next submittal all required documents are resubmitted. The latest submittal is missing the following: a. Steel building plans b. Steel building calculations c. Foundation calculations Sheet SP1.0 1. Addressed. 2. Addressed. 3. Addressed. Sheet A1.0 1. Addressed. 2. Addressed. 3. Addressed. STRUCTURAL COMMENTS Sheet S1.0 1. Addressed. MECHANICAL COMMENTS There are no comments. PLUMBING COMMENTS Sheet P1.0 1. Addressed. ELECTRICAL COMMENTS General 1. Addressed. 2. Addressed. Sheet E1.0 1. Addressed. 2. Addressed. 3. Addressed. |
||
| 07/31/2025 | Commercial Plumbing Standard | REQUIRES RESUBMIT | July 31, 2025 3rd Review ASI Architects Attn: Phillip Veneziano 5931 E. Pima Street Tucson, Arizona 85712 Re: KOCH WAREHOUSE NEW BUILDING City of Tucson Permit Number: TC-COM-0325-00482 Stantec Project Number: 185215066 Stantec File Number: TUC-25-034 Plan review for the above referenced project has been completed. This letter reflects comments to be addressed. PLEASE send all response to comments back to the City through the permit portal! Responses sent directly to Stantec will be ignored. Also, please submit complete copies of all permit documents (i.e. plans, calculations, reports, etc.) even if they have not been changed. Please cloud and delta all changes and provide a letter with a written response to each of the comments indicating the action taken. The scope of this review covers the architectural, structural, plumbing, mechanical, and electrical designs as they relate to the codes adopted by the jurisdiction. All features were checked only to the extent allowed by the submittals provided. All portions of this project are assumed to meet or will meet other departmental requirements, conditions, and concerns before permit approval. Occupancy Group Construction Type Area (Square feet) Occupant Load Automatic Fire Sprinklers Fire Alarms S-1 V-B 5,000 10 No No Separate Permits: None. Deferred Submittals: None. Special Inspections: Earthwork, concrete, and high-strength bolts. ARCHITECTURAL COMMENTS Sheet G1.0 1. Addressed. 2. Previous Comment: A special inspection certificate was not provided for the listed special inspections on the cover sheet for earthwork, concrete, and high-strength bolts. Please provide a special inspection certificate with Parts A and B completed. Still Required: The special inspection certificates provided do not contain special inspection for high-strength bolting. Please provide. 3. Addressed. 4. Addressed. 5. Addressed. 6. Addressed. 7. New Comment: Sheet SP1.0 is missing from the plan set. Please resubmit all sheets included in the plan set. 8. New Comment: The latest submittal is missing documents. Please ensure on the next submittal all required documents are resubmitted. The latest submittal is missing the following: a. Steel building plans b. Steel building calculations c. Foundation calculations Sheet SP1.0 1. Addressed. 2. Addressed. 3. Addressed. Sheet A1.0 1. Addressed. 2. Addressed. 3. Addressed. STRUCTURAL COMMENTS Sheet S1.0 1. Addressed. MECHANICAL COMMENTS There are no comments. PLUMBING COMMENTS Sheet P1.0 1. Addressed. ELECTRICAL COMMENTS General 1. Addressed. 2. Addressed. Sheet E1.0 1. Addressed. 2. Addressed. 3. Addressed. |
||
| 07/31/2025 | Outdoor Lighting Standard | REQUIRES RESUBMIT | July 31, 2025 3rd Review ASI Architects Attn: Phillip Veneziano 5931 E. Pima Street Tucson, Arizona 85712 Re: KOCH WAREHOUSE NEW BUILDING City of Tucson Permit Number: TC-COM-0325-00482 Stantec Project Number: 185215066 Stantec File Number: TUC-25-034 Plan review for the above referenced project has been completed. This letter reflects comments to be addressed. PLEASE send all response to comments back to the City through the permit portal! Responses sent directly to Stantec will be ignored. Also, please submit complete copies of all permit documents (i.e. plans, calculations, reports, etc.) even if they have not been changed. Please cloud and delta all changes and provide a letter with a written response to each of the comments indicating the action taken. The scope of this review covers the architectural, structural, plumbing, mechanical, and electrical designs as they relate to the codes adopted by the jurisdiction. All features were checked only to the extent allowed by the submittals provided. All portions of this project are assumed to meet or will meet other departmental requirements, conditions, and concerns before permit approval. Occupancy Group Construction Type Area (Square feet) Occupant Load Automatic Fire Sprinklers Fire Alarms S-1 V-B 5,000 10 No No Separate Permits: None. Deferred Submittals: None. Special Inspections: Earthwork, concrete, and high-strength bolts. ARCHITECTURAL COMMENTS Sheet G1.0 1. Addressed. 2. Previous Comment: A special inspection certificate was not provided for the listed special inspections on the cover sheet for earthwork, concrete, and high-strength bolts. Please provide a special inspection certificate with Parts A and B completed. Still Required: The special inspection certificates provided do not contain special inspection for high-strength bolting. Please provide. 3. Addressed. 4. Addressed. 5. Addressed. 6. Addressed. 7. New Comment: Sheet SP1.0 is missing from the plan set. Please resubmit all sheets included in the plan set. 8. New Comment: The latest submittal is missing documents. Please ensure on the next submittal all required documents are resubmitted. The latest submittal is missing the following: a. Steel building plans b. Steel building calculations c. Foundation calculations Sheet SP1.0 1. Addressed. 2. Addressed. 3. Addressed. Sheet A1.0 1. Addressed. 2. Addressed. 3. Addressed. STRUCTURAL COMMENTS Sheet S1.0 1. Addressed. MECHANICAL COMMENTS There are no comments. PLUMBING COMMENTS Sheet P1.0 1. Addressed. ELECTRICAL COMMENTS General 1. Addressed. 2. Addressed. Sheet E1.0 1. Addressed. 2. Addressed. 3. Addressed. |
||
| 08/08/2025 | Site Engineering Standard | REQUIRES RESUBMIT | Permit: TC-COM-0325-00482 Location: 523 E GAY ST Review Date: 8/8/2025 Site Engineering Comments: 1. Site Engineering will be unable to review and approve permit TC-COM-0325-00482 until the associated development package TD-DEV-0725-00200 is approved by all reviewers. If you have any questions or concerns, please contact Marco Contreras Marco.contreras@tucsonaz.gov |
||
| 08/14/2025 | Site Zoning Standard | REQUIRES RESUBMIT | PDSD TRANSMITTAL FROM: Bobby Parsons Zoning Section Review PROJECT: TC-COM-0325-00482 – TD-DEV-0725-00200 523 E. Gay St. Tucson, AZ 85705 New Warehouse Building (3rd Review) TRANSMITTAL DATE: 8/14/2025 This site is located in the C-2 zone (UDC 4.7.21). Comments: Please resubmit revised drawings along with a detailed response letter which states how all Zoning Review Section comments were addressed. 1. Comment: Zoning has reviewed the warehouse plans for compliance with Development Package (DP) TD-DEV-0725-00200 and although the plans appear to match, until the DP is approved by all review agencies Zoning cannot approve this permit. 2. Comment: Additional comments may be forthcoming on the next review based on the plans submitted and responses to zoning review comments. If you have any questions about this transmittal, please contact Bobby Parsons at Robert.Parsons@tucsonaz.gov. |
||
| 07/30/2025 | PDSD Application Completeness Express | REVIEW COMPLETED |