Permit Number: TC-COM-0325-00482
Parcel: 106012190

Address:
523 E GAY ST

Review Status: Requires Resubmit

Review Details: COMMERCIAL REVIEW - FULL v.3

Permit Number - TC-COM-0325-00482
Review Name: COMMERCIAL REVIEW - FULL v.3
Review Status: Requires Resubmit
Review Date Reviewer's Name Type of Review Description Status Comments
08/14/2025 Bldg Permits - Post Review Express PENDING ASSIGNMENT
07/31/2025 Commercial Building Standard REQUIRES RESUBMIT July 31, 2025
3rd Review

ASI Architects
Attn: Phillip Veneziano
5931 E. Pima Street
Tucson, Arizona 85712

Re: KOCH WAREHOUSE
NEW BUILDING

City of Tucson Permit Number: TC-COM-0325-00482
Stantec Project Number: 185215066
Stantec File Number: TUC-25-034

Plan review for the above referenced project has been completed. This letter reflects comments to be addressed. PLEASE send all response to comments back to the City through the permit portal! Responses sent directly to Stantec will be ignored. Also, please submit complete copies of all permit documents (i.e. plans, calculations, reports, etc.) even if they have not been changed. Please cloud and delta all changes and provide a letter with a written response to each of the comments indicating the action taken.

The scope of this review covers the architectural, structural, plumbing, mechanical, and electrical designs as they relate to the codes adopted by the jurisdiction. All features were checked only to the extent allowed by the submittals provided. All portions of this project are assumed to meet or will meet other departmental requirements, conditions, and concerns before permit approval.

Occupancy
Group Construction
Type Area
(Square feet) Occupant
Load Automatic
Fire Sprinklers Fire
Alarms
S-1 V-B 5,000 10 No No
Separate Permits: None.
Deferred Submittals: None.
Special Inspections: Earthwork, concrete, and high-strength bolts.

ARCHITECTURAL COMMENTS

Sheet G1.0

1. Addressed.

2. Previous Comment: A special inspection certificate was not provided for the listed special inspections on the cover sheet for earthwork, concrete, and high-strength bolts. Please provide a special inspection certificate with Parts A and B completed. Still Required: The special inspection certificates provided do not contain special inspection for high-strength bolting. Please provide.

3. Addressed.

4. Addressed.

5. Addressed.

6. Addressed.

7. New Comment: Sheet SP1.0 is missing from the plan set. Please resubmit all sheets included in the plan set.

8. New Comment: The latest submittal is missing documents. Please ensure on the next submittal all required documents are resubmitted. The latest submittal is missing the following:

a. Steel building plans
b. Steel building calculations
c. Foundation calculations

Sheet SP1.0

1. Addressed.

2. Addressed.

3. Addressed.

Sheet A1.0

1. Addressed.

2. Addressed.

3. Addressed.

STRUCTURAL COMMENTS

Sheet S1.0

1. Addressed.

MECHANICAL COMMENTS

There are no comments.

PLUMBING COMMENTS

Sheet P1.0

1. Addressed.

ELECTRICAL COMMENTS

General

1. Addressed.

2. Addressed.

Sheet E1.0

1. Addressed.

2. Addressed.

3. Addressed.
07/31/2025 Commercial Electrical Standard REQUIRES RESUBMIT July 31, 2025
3rd Review

ASI Architects
Attn: Phillip Veneziano
5931 E. Pima Street
Tucson, Arizona 85712

Re: KOCH WAREHOUSE
NEW BUILDING

City of Tucson Permit Number: TC-COM-0325-00482
Stantec Project Number: 185215066
Stantec File Number: TUC-25-034

Plan review for the above referenced project has been completed. This letter reflects comments to be addressed. PLEASE send all response to comments back to the City through the permit portal! Responses sent directly to Stantec will be ignored. Also, please submit complete copies of all permit documents (i.e. plans, calculations, reports, etc.) even if they have not been changed. Please cloud and delta all changes and provide a letter with a written response to each of the comments indicating the action taken.

The scope of this review covers the architectural, structural, plumbing, mechanical, and electrical designs as they relate to the codes adopted by the jurisdiction. All features were checked only to the extent allowed by the submittals provided. All portions of this project are assumed to meet or will meet other departmental requirements, conditions, and concerns before permit approval.

Occupancy
Group Construction
Type Area
(Square feet) Occupant
Load Automatic
Fire Sprinklers Fire
Alarms
S-1 V-B 5,000 10 No No
Separate Permits: None.
Deferred Submittals: None.
Special Inspections: Earthwork, concrete, and high-strength bolts.

ARCHITECTURAL COMMENTS

Sheet G1.0

1. Addressed.

2. Previous Comment: A special inspection certificate was not provided for the listed special inspections on the cover sheet for earthwork, concrete, and high-strength bolts. Please provide a special inspection certificate with Parts A and B completed. Still Required: The special inspection certificates provided do not contain special inspection for high-strength bolting. Please provide.

3. Addressed.

4. Addressed.

5. Addressed.

6. Addressed.

7. New Comment: Sheet SP1.0 is missing from the plan set. Please resubmit all sheets included in the plan set.

8. New Comment: The latest submittal is missing documents. Please ensure on the next submittal all required documents are resubmitted. The latest submittal is missing the following:

a. Steel building plans
b. Steel building calculations
c. Foundation calculations

Sheet SP1.0

1. Addressed.

2. Addressed.

3. Addressed.

Sheet A1.0

1. Addressed.

2. Addressed.

3. Addressed.

STRUCTURAL COMMENTS

Sheet S1.0

1. Addressed.

MECHANICAL COMMENTS

There are no comments.

PLUMBING COMMENTS

Sheet P1.0

1. Addressed.

ELECTRICAL COMMENTS

General

1. Addressed.

2. Addressed.

Sheet E1.0

1. Addressed.

2. Addressed.

3. Addressed.
07/31/2025 Commercial Mechanical Standard REQUIRES RESUBMIT July 31, 2025
3rd Review

ASI Architects
Attn: Phillip Veneziano
5931 E. Pima Street
Tucson, Arizona 85712

Re: KOCH WAREHOUSE
NEW BUILDING

City of Tucson Permit Number: TC-COM-0325-00482
Stantec Project Number: 185215066
Stantec File Number: TUC-25-034

Plan review for the above referenced project has been completed. This letter reflects comments to be addressed. PLEASE send all response to comments back to the City through the permit portal! Responses sent directly to Stantec will be ignored. Also, please submit complete copies of all permit documents (i.e. plans, calculations, reports, etc.) even if they have not been changed. Please cloud and delta all changes and provide a letter with a written response to each of the comments indicating the action taken.

The scope of this review covers the architectural, structural, plumbing, mechanical, and electrical designs as they relate to the codes adopted by the jurisdiction. All features were checked only to the extent allowed by the submittals provided. All portions of this project are assumed to meet or will meet other departmental requirements, conditions, and concerns before permit approval.

Occupancy
Group Construction
Type Area
(Square feet) Occupant
Load Automatic
Fire Sprinklers Fire
Alarms
S-1 V-B 5,000 10 No No
Separate Permits: None.
Deferred Submittals: None.
Special Inspections: Earthwork, concrete, and high-strength bolts.

ARCHITECTURAL COMMENTS

Sheet G1.0

1. Addressed.

2. Previous Comment: A special inspection certificate was not provided for the listed special inspections on the cover sheet for earthwork, concrete, and high-strength bolts. Please provide a special inspection certificate with Parts A and B completed. Still Required: The special inspection certificates provided do not contain special inspection for high-strength bolting. Please provide.

3. Addressed.

4. Addressed.

5. Addressed.

6. Addressed.

7. New Comment: Sheet SP1.0 is missing from the plan set. Please resubmit all sheets included in the plan set.

8. New Comment: The latest submittal is missing documents. Please ensure on the next submittal all required documents are resubmitted. The latest submittal is missing the following:

a. Steel building plans
b. Steel building calculations
c. Foundation calculations

Sheet SP1.0

1. Addressed.

2. Addressed.

3. Addressed.

Sheet A1.0

1. Addressed.

2. Addressed.

3. Addressed.

STRUCTURAL COMMENTS

Sheet S1.0

1. Addressed.

MECHANICAL COMMENTS

There are no comments.

PLUMBING COMMENTS

Sheet P1.0

1. Addressed.

ELECTRICAL COMMENTS

General

1. Addressed.

2. Addressed.

Sheet E1.0

1. Addressed.

2. Addressed.

3. Addressed.
07/31/2025 Commercial Plumbing Standard REQUIRES RESUBMIT July 31, 2025
3rd Review

ASI Architects
Attn: Phillip Veneziano
5931 E. Pima Street
Tucson, Arizona 85712

Re: KOCH WAREHOUSE
NEW BUILDING

City of Tucson Permit Number: TC-COM-0325-00482
Stantec Project Number: 185215066
Stantec File Number: TUC-25-034

Plan review for the above referenced project has been completed. This letter reflects comments to be addressed. PLEASE send all response to comments back to the City through the permit portal! Responses sent directly to Stantec will be ignored. Also, please submit complete copies of all permit documents (i.e. plans, calculations, reports, etc.) even if they have not been changed. Please cloud and delta all changes and provide a letter with a written response to each of the comments indicating the action taken.

The scope of this review covers the architectural, structural, plumbing, mechanical, and electrical designs as they relate to the codes adopted by the jurisdiction. All features were checked only to the extent allowed by the submittals provided. All portions of this project are assumed to meet or will meet other departmental requirements, conditions, and concerns before permit approval.

Occupancy
Group Construction
Type Area
(Square feet) Occupant
Load Automatic
Fire Sprinklers Fire
Alarms
S-1 V-B 5,000 10 No No
Separate Permits: None.
Deferred Submittals: None.
Special Inspections: Earthwork, concrete, and high-strength bolts.

ARCHITECTURAL COMMENTS

Sheet G1.0

1. Addressed.

2. Previous Comment: A special inspection certificate was not provided for the listed special inspections on the cover sheet for earthwork, concrete, and high-strength bolts. Please provide a special inspection certificate with Parts A and B completed. Still Required: The special inspection certificates provided do not contain special inspection for high-strength bolting. Please provide.

3. Addressed.

4. Addressed.

5. Addressed.

6. Addressed.

7. New Comment: Sheet SP1.0 is missing from the plan set. Please resubmit all sheets included in the plan set.

8. New Comment: The latest submittal is missing documents. Please ensure on the next submittal all required documents are resubmitted. The latest submittal is missing the following:

a. Steel building plans
b. Steel building calculations
c. Foundation calculations

Sheet SP1.0

1. Addressed.

2. Addressed.

3. Addressed.

Sheet A1.0

1. Addressed.

2. Addressed.

3. Addressed.

STRUCTURAL COMMENTS

Sheet S1.0

1. Addressed.

MECHANICAL COMMENTS

There are no comments.

PLUMBING COMMENTS

Sheet P1.0

1. Addressed.

ELECTRICAL COMMENTS

General

1. Addressed.

2. Addressed.

Sheet E1.0

1. Addressed.

2. Addressed.

3. Addressed.
07/31/2025 Outdoor Lighting Standard REQUIRES RESUBMIT July 31, 2025
3rd Review

ASI Architects
Attn: Phillip Veneziano
5931 E. Pima Street
Tucson, Arizona 85712

Re: KOCH WAREHOUSE
NEW BUILDING

City of Tucson Permit Number: TC-COM-0325-00482
Stantec Project Number: 185215066
Stantec File Number: TUC-25-034

Plan review for the above referenced project has been completed. This letter reflects comments to be addressed. PLEASE send all response to comments back to the City through the permit portal! Responses sent directly to Stantec will be ignored. Also, please submit complete copies of all permit documents (i.e. plans, calculations, reports, etc.) even if they have not been changed. Please cloud and delta all changes and provide a letter with a written response to each of the comments indicating the action taken.

The scope of this review covers the architectural, structural, plumbing, mechanical, and electrical designs as they relate to the codes adopted by the jurisdiction. All features were checked only to the extent allowed by the submittals provided. All portions of this project are assumed to meet or will meet other departmental requirements, conditions, and concerns before permit approval.

Occupancy
Group Construction
Type Area
(Square feet) Occupant
Load Automatic
Fire Sprinklers Fire
Alarms
S-1 V-B 5,000 10 No No
Separate Permits: None.
Deferred Submittals: None.
Special Inspections: Earthwork, concrete, and high-strength bolts.

ARCHITECTURAL COMMENTS

Sheet G1.0

1. Addressed.

2. Previous Comment: A special inspection certificate was not provided for the listed special inspections on the cover sheet for earthwork, concrete, and high-strength bolts. Please provide a special inspection certificate with Parts A and B completed. Still Required: The special inspection certificates provided do not contain special inspection for high-strength bolting. Please provide.

3. Addressed.

4. Addressed.

5. Addressed.

6. Addressed.

7. New Comment: Sheet SP1.0 is missing from the plan set. Please resubmit all sheets included in the plan set.

8. New Comment: The latest submittal is missing documents. Please ensure on the next submittal all required documents are resubmitted. The latest submittal is missing the following:

a. Steel building plans
b. Steel building calculations
c. Foundation calculations

Sheet SP1.0

1. Addressed.

2. Addressed.

3. Addressed.

Sheet A1.0

1. Addressed.

2. Addressed.

3. Addressed.

STRUCTURAL COMMENTS

Sheet S1.0

1. Addressed.

MECHANICAL COMMENTS

There are no comments.

PLUMBING COMMENTS

Sheet P1.0

1. Addressed.

ELECTRICAL COMMENTS

General

1. Addressed.

2. Addressed.

Sheet E1.0

1. Addressed.

2. Addressed.

3. Addressed.
08/08/2025 Site Engineering Standard REQUIRES RESUBMIT Permit: TC-COM-0325-00482
Location: 523 E GAY ST
Review Date: 8/8/2025
Site Engineering Comments:
1. Site Engineering will be unable to review and approve permit TC-COM-0325-00482 until the associated development package TD-DEV-0725-00200 is approved by all reviewers.

If you have any questions or concerns, please contact
Marco Contreras
Marco.contreras@tucsonaz.gov
08/14/2025 Site Zoning Standard REQUIRES RESUBMIT PDSD TRANSMITTAL

FROM:
Bobby Parsons
Zoning Section Review

PROJECT:
TC-COM-0325-00482 – TD-DEV-0725-00200
523 E. Gay St. Tucson, AZ 85705
New Warehouse Building (3rd Review)

TRANSMITTAL DATE: 8/14/2025

This site is located in the C-2 zone (UDC 4.7.21).

Comments: Please resubmit revised drawings along with a detailed response letter which states how all Zoning Review Section comments were addressed.

1. Comment: Zoning has reviewed the warehouse plans for compliance with Development Package (DP) TD-DEV-0725-00200 and although the plans appear to match, until the DP is approved by all review agencies Zoning cannot approve this permit.
2. Comment: Additional comments may be forthcoming on the next review based on the plans submitted and responses to zoning review comments.

If you have any questions about this transmittal, please contact Bobby Parsons at Robert.Parsons@tucsonaz.gov.
07/30/2025 PDSD Application Completeness Express REVIEW COMPLETED