Permit Review Detail
Review Status: Requires Resubmit
Review Details: COMMERCIAL REVIEW - LIMITED v.1
Permit Number - TC-COM-0325-00471
Review Name: COMMERCIAL REVIEW - LIMITED v.1
Review Status: Requires Resubmit
Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
---|---|---|---|---|---|
03/24/2025 | Commercial Building | APPROVED | |||
03/14/2025 | Commercial Electrical | APPROVED | |||
03/25/2025 | Commercial Mechanical | APPROVED | |||
03/25/2025 | Site Zoning | APPROVED | |||
03/25/2025 | Water - PDSD | APPROVED | |||
03/25/2025 | Bldg Permits - Post Review Express | PENDING ASSIGNMENT | |||
03/25/2025 | Commercial Plumbing | REQUIRES RESUBMIT | Verify that the distance from the hot water source to the hot water termination for the public lavatories complies with the requirements of Section C404.5, IECC 2018. | ||
03/13/2025 | Fire New Construction | REQUIRES RESUBMIT | Required Items: 1. The City of Tucson Adopted Current Fire Code is the 2024 International Fire Code with local amendments, check the project for compliance and update code at Building Code Information page G1.1 2. Page A2.1: Door 103 B swings into Exit door 103C. Check compliance and provide measurements accordingly with the 2018 International Building Code Chapter 10, section 1005.7 3. Any upgrade to fire alarm or fire sprinklers requires a separate permit. ( If Applicable) |
||
03/14/2025 | Outdoor Lighting | REQUIRES RESUBMIT | Outdoor Lighting Review TC-COM-0325-00471 (35 E TOOLE AV TUCSON, AZ 85701) Plan review for the above referenced structure has been completed. This letter reflects comments to be addressed. Provide updated Plans/calculations and a written response Letter to each of the notated items indicating action taken. Resubmitted plans that do not contain a written response Letter addressing each of the notated items indicating action taken, may be delayed until response letter is received. Code reference, 2018 International Building Code (IBC), 2017 National Electrical Code (NEC), 2012 Outdoor Lighting Code (OLC). https://www.tucsonaz.gov/files/sharedassets/public/v/1/pdsd/documents/building-code/2012_outdoor_lighting_code_.pdf Outdoor Lighting Review: 1. Provide an outdoor lighting plan that meets the requirements of OLC 104.2. Show/locate the different light sources on your site plan. Number/label the light fixtures on your table and use the same number on your site plan for both internal and external lights. 2. Clarify if any outdoor lighting is being added or modified and provide the following if changes are being made: a. Show compliance with City of Tucson Outdoor Lighting Code with an approved lighting calculation in accordance with OLC 3.1.2. Include all exterior fixtures on the property in the calculations. Show unshielded fixtures with a maximum of 3,000 lumens, OLC 401.4. Show lamps with a maximum of 3500K color temperature, OLC 402.1. b. Show compliance to total outdoor light output per 2012 City of Tucson/Pima County Outdoor Lighting Code section 401.2. Total outdoor light output shall not exceed the lumen limits listed in Table 401.1. 4. E1.1 – Lighting Code section 104.2.2. c. Submit catalogue or specification sheets of all proposed new outdoor lighting fixtures illustrating the type of fixture, color temperature, lumens rating and whether full cut-off or unshielded. Contact Jeremy Hamblin with any questions: Jeremy.hamblin@tucsonaz.gov |
||
03/12/2025 | PDSD Application Completeness Express | REVIEW COMPLETED |