Permit Number: TC-COM-0325-00427
Parcel: 140420760

Review Status: Requires Resubmit

Review Details: COMMERCIAL REVIEW - FULL REVISION v.1

Permit Number - TC-COM-0325-00427
Review Name: COMMERCIAL REVIEW - FULL REVISION v.1
Review Status: Requires Resubmit
Review Date Reviewer's Name Type of Review Description Status Comments
12/19/2025 Site Zoning Standard APPROVED
12/22/2025 Water - PDSD Standard APPROVED
12/10/2025 Outdoor Lighting Standard NOT REQUIRED No modifications to the outdoor lighting.
12/04/2025 Site Engineering Standard NOT REQUIRED
12/23/2025 Bldg Permits - Post Review Express PENDING ASSIGNMENT
12/10/2025 Commercial Building Standard REQUIRES RESUBMIT December 10, 2025
1st Review

Seaver Franks
Attn: Nurlan Herburger
2552 N. Alvernon Way
Tucson, Arizona 85712

Re: CORD BLOOD REGISTRY - DEWAR
ADDITION AND TENANT IMPROVEMENT (REVISIONS)

City of Tucson Permit Number: TC-COM-0325-00427
Stantec Project Number: 185215066
Stantec File Number: TUC-25-107

Plan review for the above referenced project has been completed. This letter reflects comments to be addressed. PLEASE send all response to comments back to the City through the permit portal! Responses sent directly to Stantec will be ignored. Also, please submit complete copies of all permit documents (i.e. plans, calculations, reports, etc.) even if they have not been changed. Please cloud and delta all changes and provide a letter with a written response to each of the comments indicating the action taken.

The scope of this review covers the architectural, structural, plumbing, mechanical, and electrical designs as they relate to the codes adopted by the jurisdiction. All features were checked only to the extent allowed by the submittals provided. All portions of this project are assumed to meet or will meet other departmental requirements, conditions, and concerns before permit approval.

Occupancy
Group Construction
Type Area
(Square feet) Occupant
Load Automatic
Fire Sprinklers Fire
Alarms
B III-B 36,747 286 Yes Yes
S-2
Separate Permits: Automatic fire sprinklers and fire alarm.
Deferred Submittals: None.
Special Inspections: Earthwork, concrete, epoxy and expansion anchors, field welding, and masonry.

ARCHITECTURAL COMMENTS

Sheet A2.0

1. The walls of the interior exit stairway “New Stairwell 120-6” are not indicated as being fire rated. Interior exit stairway enclosures shall be constructed as fire barriers with a fire-resistance rating of 1-hour when connecting four or less stories. Please provide a listed assembly for the walls. [Ref. IBC 2018 1023.2]

Sheet A6.0

1. The fire barriers enclosing the interior exit stairway indicate them terminating at the bottom of the I-joists. Fire barriers must terminate at the underside of the roof deck. Please revise. [Ref. IBC 2018 Sec. 707.5]

Sheet A10.0

1. Please indicate all doors at the new interior exit stair to be 1-hour rated and self-closing. [Ref. IBC 2018 Sec. 716.1(2)]

STRUCTURAL COMMENTS

There are no comments.

MECHANICAL COMMENTS

Sheet M1.1

1. The plans indicate a register at the interior exit stairway “120-6”. This register is part of the building’s ventilation system. Interior exit stairway ventilation systems must be independent of other building ventilation systems. Please remove the register from the stairway. [Ref. IBC 2018 Sec. 1023.6]

Sheet M1.2

1. The plans indicate a register at the interior exit stairway “120-6”. This register is part of the building’s ventilation system. Interior exit stairway ventilation systems must be independent of other building ventilation systems. Please remove the register from the stairway. [Ref. IBC 2018 Sec. 1023.6]

2. The plans indicate a duct running through the interior exit stairway. The only ductwork allowed within an interior exit stairway is what is necessary for the independent ventilation system. Please remove the duct from the interior exit stairway. [Ref. IBC 2018 Sec. 1023.5]

PLUMBING COMMENTS

There are no comments.

ELECTRICAL COMMENTS

There are no comments.


Should you have any questions regarding the plan review comments, please contact the plan reviewer listed for the appropriate discipline.

Plans reviewed by:
Trevor Bies,
Senior Plan Reviewer
602-338-9922
trevor.bies@stantec.com
12/10/2025 Commercial Electrical Standard REQUIRES RESUBMIT December 10, 2025
1st Review

Seaver Franks
Attn: Nurlan Herburger
2552 N. Alvernon Way
Tucson, Arizona 85712

Re: CORD BLOOD REGISTRY - DEWAR
ADDITION AND TENANT IMPROVEMENT (REVISIONS)

City of Tucson Permit Number: TC-COM-0325-00427
Stantec Project Number: 185215066
Stantec File Number: TUC-25-107

Plan review for the above referenced project has been completed. This letter reflects comments to be addressed. PLEASE send all response to comments back to the City through the permit portal! Responses sent directly to Stantec will be ignored. Also, please submit complete copies of all permit documents (i.e. plans, calculations, reports, etc.) even if they have not been changed. Please cloud and delta all changes and provide a letter with a written response to each of the comments indicating the action taken.

The scope of this review covers the architectural, structural, plumbing, mechanical, and electrical designs as they relate to the codes adopted by the jurisdiction. All features were checked only to the extent allowed by the submittals provided. All portions of this project are assumed to meet or will meet other departmental requirements, conditions, and concerns before permit approval.

Occupancy
Group Construction
Type Area
(Square feet) Occupant
Load Automatic
Fire Sprinklers Fire
Alarms
B III-B 36,747 286 Yes Yes
S-2
Separate Permits: Automatic fire sprinklers and fire alarm.
Deferred Submittals: None.
Special Inspections: Earthwork, concrete, epoxy and expansion anchors, field welding, and masonry.

ARCHITECTURAL COMMENTS

Sheet A2.0

1. The walls of the interior exit stairway “New Stairwell 120-6” are not indicated as being fire rated. Interior exit stairway enclosures shall be constructed as fire barriers with a fire-resistance rating of 1-hour when connecting four or less stories. Please provide a listed assembly for the walls. [Ref. IBC 2018 1023.2]

Sheet A6.0

1. The fire barriers enclosing the interior exit stairway indicate them terminating at the bottom of the I-joists. Fire barriers must terminate at the underside of the roof deck. Please revise. [Ref. IBC 2018 Sec. 707.5]

Sheet A10.0

1. Please indicate all doors at the new interior exit stair to be 1-hour rated and self-closing. [Ref. IBC 2018 Sec. 716.1(2)]

STRUCTURAL COMMENTS

There are no comments.

MECHANICAL COMMENTS

Sheet M1.1

1. The plans indicate a register at the interior exit stairway “120-6”. This register is part of the building’s ventilation system. Interior exit stairway ventilation systems must be independent of other building ventilation systems. Please remove the register from the stairway. [Ref. IBC 2018 Sec. 1023.6]

Sheet M1.2

1. The plans indicate a register at the interior exit stairway “120-6”. This register is part of the building’s ventilation system. Interior exit stairway ventilation systems must be independent of other building ventilation systems. Please remove the register from the stairway. [Ref. IBC 2018 Sec. 1023.6]

2. The plans indicate a duct running through the interior exit stairway. The only ductwork allowed within an interior exit stairway is what is necessary for the independent ventilation system. Please remove the duct from the interior exit stairway. [Ref. IBC 2018 Sec. 1023.5]

PLUMBING COMMENTS

There are no comments.

ELECTRICAL COMMENTS

There are no comments.


Should you have any questions regarding the plan review comments, please contact the plan reviewer listed for the appropriate discipline.

Plans reviewed by:
Trevor Bies,
Senior Plan Reviewer
602-338-9922
trevor.bies@stantec.com
12/10/2025 Commercial Mechanical Standard REQUIRES RESUBMIT December 10, 2025
1st Review

Seaver Franks
Attn: Nurlan Herburger
2552 N. Alvernon Way
Tucson, Arizona 85712

Re: CORD BLOOD REGISTRY - DEWAR
ADDITION AND TENANT IMPROVEMENT (REVISIONS)

City of Tucson Permit Number: TC-COM-0325-00427
Stantec Project Number: 185215066
Stantec File Number: TUC-25-107

Plan review for the above referenced project has been completed. This letter reflects comments to be addressed. PLEASE send all response to comments back to the City through the permit portal! Responses sent directly to Stantec will be ignored. Also, please submit complete copies of all permit documents (i.e. plans, calculations, reports, etc.) even if they have not been changed. Please cloud and delta all changes and provide a letter with a written response to each of the comments indicating the action taken.

The scope of this review covers the architectural, structural, plumbing, mechanical, and electrical designs as they relate to the codes adopted by the jurisdiction. All features were checked only to the extent allowed by the submittals provided. All portions of this project are assumed to meet or will meet other departmental requirements, conditions, and concerns before permit approval.

Occupancy
Group Construction
Type Area
(Square feet) Occupant
Load Automatic
Fire Sprinklers Fire
Alarms
B III-B 36,747 286 Yes Yes
S-2
Separate Permits: Automatic fire sprinklers and fire alarm.
Deferred Submittals: None.
Special Inspections: Earthwork, concrete, epoxy and expansion anchors, field welding, and masonry.

ARCHITECTURAL COMMENTS

Sheet A2.0

1. The walls of the interior exit stairway “New Stairwell 120-6” are not indicated as being fire rated. Interior exit stairway enclosures shall be constructed as fire barriers with a fire-resistance rating of 1-hour when connecting four or less stories. Please provide a listed assembly for the walls. [Ref. IBC 2018 1023.2]

Sheet A6.0

1. The fire barriers enclosing the interior exit stairway indicate them terminating at the bottom of the I-joists. Fire barriers must terminate at the underside of the roof deck. Please revise. [Ref. IBC 2018 Sec. 707.5]

Sheet A10.0

1. Please indicate all doors at the new interior exit stair to be 1-hour rated and self-closing. [Ref. IBC 2018 Sec. 716.1(2)]

STRUCTURAL COMMENTS

There are no comments.

MECHANICAL COMMENTS

Sheet M1.1

1. The plans indicate a register at the interior exit stairway “120-6”. This register is part of the building’s ventilation system. Interior exit stairway ventilation systems must be independent of other building ventilation systems. Please remove the register from the stairway. [Ref. IBC 2018 Sec. 1023.6]

Sheet M1.2

1. The plans indicate a register at the interior exit stairway “120-6”. This register is part of the building’s ventilation system. Interior exit stairway ventilation systems must be independent of other building ventilation systems. Please remove the register from the stairway. [Ref. IBC 2018 Sec. 1023.6]

2. The plans indicate a duct running through the interior exit stairway. The only ductwork allowed within an interior exit stairway is what is necessary for the independent ventilation system. Please remove the duct from the interior exit stairway. [Ref. IBC 2018 Sec. 1023.5]

PLUMBING COMMENTS

There are no comments.

ELECTRICAL COMMENTS

There are no comments.


Should you have any questions regarding the plan review comments, please contact the plan reviewer listed for the appropriate discipline.

Plans reviewed by:
Trevor Bies,
Senior Plan Reviewer
602-338-9922
trevor.bies@stantec.com
12/10/2025 Commercial Plumbing Standard REQUIRES RESUBMIT December 10, 2025
1st Review

Seaver Franks
Attn: Nurlan Herburger
2552 N. Alvernon Way
Tucson, Arizona 85712

Re: CORD BLOOD REGISTRY - DEWAR
ADDITION AND TENANT IMPROVEMENT (REVISIONS)

City of Tucson Permit Number: TC-COM-0325-00427
Stantec Project Number: 185215066
Stantec File Number: TUC-25-107

Plan review for the above referenced project has been completed. This letter reflects comments to be addressed. PLEASE send all response to comments back to the City through the permit portal! Responses sent directly to Stantec will be ignored. Also, please submit complete copies of all permit documents (i.e. plans, calculations, reports, etc.) even if they have not been changed. Please cloud and delta all changes and provide a letter with a written response to each of the comments indicating the action taken.

The scope of this review covers the architectural, structural, plumbing, mechanical, and electrical designs as they relate to the codes adopted by the jurisdiction. All features were checked only to the extent allowed by the submittals provided. All portions of this project are assumed to meet or will meet other departmental requirements, conditions, and concerns before permit approval.

Occupancy
Group Construction
Type Area
(Square feet) Occupant
Load Automatic
Fire Sprinklers Fire
Alarms
B III-B 36,747 286 Yes Yes
S-2
Separate Permits: Automatic fire sprinklers and fire alarm.
Deferred Submittals: None.
Special Inspections: Earthwork, concrete, epoxy and expansion anchors, field welding, and masonry.

ARCHITECTURAL COMMENTS

Sheet A2.0

1. The walls of the interior exit stairway “New Stairwell 120-6” are not indicated as being fire rated. Interior exit stairway enclosures shall be constructed as fire barriers with a fire-resistance rating of 1-hour when connecting four or less stories. Please provide a listed assembly for the walls. [Ref. IBC 2018 1023.2]

Sheet A6.0

1. The fire barriers enclosing the interior exit stairway indicate them terminating at the bottom of the I-joists. Fire barriers must terminate at the underside of the roof deck. Please revise. [Ref. IBC 2018 Sec. 707.5]

Sheet A10.0

1. Please indicate all doors at the new interior exit stair to be 1-hour rated and self-closing. [Ref. IBC 2018 Sec. 716.1(2)]

STRUCTURAL COMMENTS

There are no comments.

MECHANICAL COMMENTS

Sheet M1.1

1. The plans indicate a register at the interior exit stairway “120-6”. This register is part of the building’s ventilation system. Interior exit stairway ventilation systems must be independent of other building ventilation systems. Please remove the register from the stairway. [Ref. IBC 2018 Sec. 1023.6]

Sheet M1.2

1. The plans indicate a register at the interior exit stairway “120-6”. This register is part of the building’s ventilation system. Interior exit stairway ventilation systems must be independent of other building ventilation systems. Please remove the register from the stairway. [Ref. IBC 2018 Sec. 1023.6]

2. The plans indicate a duct running through the interior exit stairway. The only ductwork allowed within an interior exit stairway is what is necessary for the independent ventilation system. Please remove the duct from the interior exit stairway. [Ref. IBC 2018 Sec. 1023.5]

PLUMBING COMMENTS

There are no comments.

ELECTRICAL COMMENTS

There are no comments.


Should you have any questions regarding the plan review comments, please contact the plan reviewer listed for the appropriate discipline.

Plans reviewed by:
Trevor Bies,
Senior Plan Reviewer
602-338-9922
trevor.bies@stantec.com
12/23/2025 Fire New Construction Standard REQUIRES RESUBMIT Resolve building review comments.
Questions: patricia.shelton@tucsonaz.gov
12/03/2025 PDSD Application Completeness Express REVIEW COMPLETED